34
Programming and installation manual Careline Anna / Careline GSM
Doc. no. 32-022-03-01 EN v6
Link Test
Has an additional submenu consisting of:
>Activation< >Interval< >Linktest 9-16<
Under
>Activation<
you can choose between five alternatives.
<Activated>
which means that the test
alarm shall be activated from the alarm transmitter.
<Recurrent>
which means that if Careline
Anna/GSM has registered a link test failure, Careline Anna/GSM will send an alert every time interval
expires until it receives a new test alarm from the alarm transmitter or that a new alarm transmitter is
programmed in the same position.
<Return alarm>
which means the same as the Activated
alternative but, you will also get an alarm when the transmitter is in contact with the carephone again.
<Recur+return>
which means the same as the Recurrent alternative but, you will also get an alarm
when the transmitter is in contact with the carephone again.
<Not activated>
means that this function
is not used. The factory default is
<Activated>.
>Interval<
defines how many hours before Careline Anna/GSM sends Lost test alarm Tx . The value
can be between 28-255 hours (factory default is 52). The alarm transmitter sends a test alarm every
23rd hour.
Under >Linktest 9-16< the link test function can be activated for transmitter positions 9-16. Link test is
only activated on position 1-8 in the default settings.
Away function
Can be set as
<Activated>
or
<Not activated>.
The away function can be used if the care recipient, for
example, shall be away from home. If the function is activated, you can then hold down the green button
for 3 seconds to set the carephone in the away mode. When this done, a message is sent to the alarm
receiver stating that the carephone is in away mode. Where the care recipient returns, they can once again
hold the green button for 3 seconds to disable the away mode. While the carephone is in away mode, no
passive alarm or link test alarm is sent. A yellow LED flashes to mark the away mode.
Mains failure
Determines the delay in hours before Careline Anna/GSM sends a loss of power alarm after a power failure.
Possible values are 0 -255 hours. The value 0 means that no loss of power alarm is sent. A value of 1
means that a loss of power alarm is sent within one hour. Practical values are between 1 and 7 hours.
Factory default is 1 hour.
Mains return
Determines if Careline Anna/GSM will send a return of power, when power is restored. If this feature is
enabled, notice of return of power is sent from Careline Anna/GSM from 5 to 35 minutes after the power
returns. The factory default is
<Not activated>.
Passive Alarm
Determines the time in hours before the passive alarm is sent. Possible values are 2 -254 hours. In practice,
this means that if the value is set to 24, the first alarm is sent after about 24 hours. The time can also be set
to 0 which means that the alarm is triggered directly for, e.g., door alarms. Factory default is 24 hours.
Extended
Has a submenu, which controls the status of all functions in the carephone.
>Presence< >Ready< >Action< >How to send< >Emergency< >Assistance< >Reminder Time<>No. of
reminders< >Prefix D< >Prefix N, V<
Presence, Ready and Action
These are used to send information to the alarm receiver that the staff have arrived at the care recipient,
has carried out an action and is ready for departure from the care recipient. These functions can be
activated or deactivated by selecting
<Activated>
or
<Not activated>
in the list that appears. A finish
signal is triggered automatically, a certain number of hours after a presence indicator, if it has not
previously been registered manually (the number of hours is programmable, the default is 8 hours).