4.5
Connecting inverter and switching AC on
DANGER
Voltage
There is a risk of death by electrocution.
►
Follow the safety instructions and warning notices in chapter 5.
DC and AC cables may interfere with data transmission.
►
Keep a distance of 200 mm between the data connecting cables
(RS485/Ethernet) and the DC/AC cables.
NOTE
If sealing caps are missing, moisture may get into the inverter.
►
Seal vacant RJ45 sockets with sealing caps.
1. If required, establish the data connection:
- Connect inverters (mater device and further connected inverters) with data connect-
ing cable(s).
- Switch on termination on the last inverter (slide switch).
2. Seal vacant RJ45 sockets with sealing caps.
3. Press DC plug firmly into the DC connection in the inverter until it engages audibly.
4. Insert AC plug into the AC connection in the inverter until it engages audibly.
5. Switch on the AC circuit breaker.
The display shows the start page of initial commissioning.
4.6
Performing initial commissioning
Any further actions required for the installation of the inverter cannot be carried out before
the initial commissioning has been performed. The initial commissioning is comprehensibly
described in chapter 5.