Dismounting the inverter
The safety instruction from chapter 5 apply.
6.1
Switching AC and DC off
1. Turn DC disconnector on the inverter to position "0".
2. Switch the AC circuit breaker off.
6.2
Disconnecting DC connection from
inverter
DANGER
Voltage can be present at the DC-connection for up to 10 minutes after
switching off the DC circuit breaker.
There is a risk of death by electrocution.
►
Wait 10 minutes after switching off the DC disconnector.
DANGER
The PV generator carries voltage when there is solar radiation.
There is a risk of death by electrocution.
►
Only have specialists carry out any work on the DC connection.
1. Disconnect plug of the DC cables as described in the instructions of the DC plug
manufacturer (refer to annex).
6.3
Disconnecting AC plug from inverter
1. Using a suitable tool, press locking hook on the AC plug slightly in and remove the
plug.
2. Ensure that none of the AC plug poles carries voltage with the help of a suitable volt-
age tester (do no use a phase testing probe).