763.134 Z02 1913 coolcept_fleX
5.4.2 Changing parameters of the nodes
The "Nodes" menu mask only appears when at least 3 nodes
have been entered.
1. Enter and confirm the desired value
for "P" and "cos ψ".
2. Return to the "Reactive power" menu with "ESC".
"P (%)" cannot be changed for the first and the last node (000 %, 100 %).
5.4.3 Displaying the reactive power characteristic curve
The characteristic curve previously entered is displayed.
1. Return to the checklist with "ESC".
5.5
Finishing the initial commissioning
1. Select "Finish" from the checklist and confirm.
If the checklist has not been processed completely, the message "Settings are incomplete"
is displayed. In this case:
1. Press "SET". The checklist is displayed again.
2. Process the open items and finish the processing.
When all settings have been processed, a dialogue stating "Are all settings correct?" is dis-
played. In this case:
1. Check the settings.
2. If any settings have to be corrected, select the correspond-
ing menu in the checklist and correct the settings.
3. If all the settings are correct: press "SET" longer. The in-
verter is restarted and synchronises itself with the grid.
After finishing the initial commissioning, you can set the feed-in management and switch
DC on (refer to section 4.7).