763.134 Z02 1913 coolcept_fleX
12.2 StecaGrid 3011_2, 3611_2 and 4611_2
StecaGrid
3011_2
StecaGrid
3611_2
StecaGrid
4611_2
Installation altitude
Max. 2000 m above sea level
DC input side (PV generator connection)
Max. input voltage
750 V
MPP voltage range
125 V to
600 V
150 V to
600 V
150 V to
600 V
Operating voltage range at nominal
power
230 V to
600 V
280 V to
600 V
360 V to
600 V
Number of MPP trackers
2
Max. input current
2 x 13 A
Max. input power with max. output
active power
3070 W
3770 W
4740 W
Max. short-circuit current
15 A
AC output side (grid connection)
Output voltage
185 V to 276 V
Nominal output voltage
230 V
Max. output current
14 A
16 A
20 A
Max. active power (cosPhi = 1)
3000 W
3680 W
4600 W
Maximum apparent power
3000 VA
3680 VA
4600 VA
Nominal power
3000 W
3680 W
4600 W
Nominal frequency
50 Hz and 60 Hz
Grid frequency
45 Hz to 65 Hz
Power loss during nighttime
operation
< 3 W
Feed-in phases
One-phase
Distortion factor (cosPhi = 1)
< 3 %
Power factor cosPhi
0.8 capacitive to 0.8 inductive
Highest output fault current
0.0 A