10-8
Parameter Specification
605C Frequency Inverter
Tag
(MMI) Name
Block
Type
Range
ID
Notes
255
SPEED DEMAND
REFERENCE
INT
xxx.xh % (h)
73
Output
256
REVERSE
REFERENCE
BOOL
FALSE / TRUE
74
Output
257
REMOTE REF
LOCAL CONTROL
BOOL
FALSE / TRUE
75
Output
258
RAMP ACCEL RATE
SYSTEM RAMP
INT
0.0 to 600.0 s
76
259
RAMP DECEL RATE
SYSTEM RAMP
INT
0.0 to 600.0 s
77
260
RAMP HOLD
SYSTEM RAMP
BOOL
FALSE / TRUE
78
261
JOG ACCEL RATE
JOG
INT
0.0 to 600.0 s
79
262
JOG DECEL RATE
JOG
INT
0.0 to 600.0 s
7a
263
STOP RATE
STOP
INT
0.0 to 600.0 s
7b
264
FAST STOP RATE
STOP
INT
0.0 to 600.0 s
7c
265
REF MODES
LOCAL CONTROL
ENUM
0 : LOCAL/REMOTE
1 : LOCAL ONLY
2 : REMOTE ONLY
7d
7
266
STOP ZERO SPEED
STOP
INT
0.00 to 100.00 %
7e
267
RAMP SYM RATE
SYSTEM RAMP
INT
0.0 to 600.0 s
7f
268
RAMP SYM MODE
SYSTEM RAMP
BOOL
FALSE / TRUE
7g
269
COMMS SETPOINT
REFERENCE
INT
-300.00 to 300.00 %
7h
1, 4, 5
270
COMMS REF
COMMS CONTROL
BOOL
FALSE / TRUE
7i
Output
272
COMMS STATUS
COMMS CONTROL
WORD
0000 to FFFF
7k
Output
273
COMMS COMMAND
COMMS CONTROL
WORD
0000 to FFFF
7l
Output
274
HEALTHY
SEQUENCING LOGIC
BOOL
FALSE / TRUE
7m
Output
275
FAST STOP LIMIT
STOP
INT
0.0 to 3000.0 s
7n
276
DRIVE ENABLE
SEQUENCING LOGIC
BOOL
FALSE / TRUE
7o
277
/FAST STOP
SEQUENCING LOGIC
BOOL
FALSE / TRUE
7p
278
/COAST STOP
SEQUENCING LOGIC
BOOL
FALSE / TRUE
7q
279
RUN STOP MODE
STOP
ENUM
0 : RAMPED
1 : COAST
2 : DC INJECTION
7r
7
280
JOG
SEQUENCING LOGIC
BOOL
FALSE / TRUE
7s
1
281
SEQ DIRECTION
LOCAL CONTROL
BOOL
FALSE / TRUE
7t
7
282
REM TRIP RESET
SEQUENCING LOGIC
BOOL
FALSE / TRUE
7u
1
283
POWER UP START
SEQUENCING LOGIC
BOOL
FALSE / TRUE
7v
284
STOP DELAY
STOP
INT
0.000 to 30.000 s
7w
285
RUNNING
SEQUENCING LOGIC
BOOL
FALSE / TRUE
7x
Output
286
OUTPUT CONTACTOR
SEQUENCING LOGIC
BOOL
FALSE / TRUE
7y
Output
287
READY
SEQUENCING LOGIC
BOOL
FALSE / TRUE
7z
Output
288
SWITCH ON ENABLE
SEQUENCING LOGIC
BOOL
FALSE / TRUE
80
Output
289
TRIPPED
SEQUENCING LOGIC
BOOL
FALSE / TRUE
81
Output
290
TRIP RST BY RUN
SEQUENCING LOGIC
BOOL
FALSE / TRUE
82
291
RUN FWD
SEQUENCING LOGIC
BOOL
FALSE / TRUE
83
1
292
RUN REV
SEQUENCING LOGIC
BOOL
FALSE / TRUE
84
1
293
/STOP
SEQUENCING LOGIC
BOOL
FALSE / TRUE
85
1
294
REMOTE REVERSE
SEQUENCING LOGIC
BOOL
FALSE / TRUE
86
295
COMMS SEQ
COMMS CONTROL
BOOL
FALSE / TRUE
87
Output
296
REMOTE REV OUT
SEQUENCING LOGIC
BOOL
FALSE / TRUE
88
Output
297
REMOTE SEQ
LOCAL CONTROL
BOOL
FALSE / TRUE
89
Output
298
SEQ MODES
LOCAL CONTROL
ENUM
Same as tag 265
8a
7
299
POWER UP MODE
LOCAL CONTROL
ENUM
0 : LOCAL
1 : REMOTE
2 : AUTOMATIC
8b
Содержание 605C
Страница 16: ...1 4 Getting Started 605C Frequency Inverter ...
Страница 22: ...2 6 An Overview of the Inverter 605C Frequency Inverter ...
Страница 50: ...4 14 Operating the Inverter 605C Frequency Inverter ...
Страница 66: ...5 16 The Operator Station 605C Frequency Inverter ...
Страница 156: ...8 2 Routine Maintenance and Repair 605C Frequency Inverter ...
Страница 184: ...10 22 Parameter Specification 605C Frequency Inverter ...
Страница 212: ...13 6 Application Notes 605C Frequency Inverter ...
Страница 214: ...14 2 Serial Communications 605C Frequency Inverter ...
Страница 236: ......