Programming Your Application
6-31
605C Frequency Inverter
Functional Description
The flycatching function enables the drive to be restarted smoothly into a spinning motor. It
applies small search voltages to the motor whilst ramping the Inverter frequency from maximum
speed to zero. When the motor load goes from motoring to regenerating, the speed search has
succeeded and is terminated. If the search frequency falls below the minimum search speed, the
speed search has failed and the Inverter will ramp to the speed setpoint from zero.
The flycatching sequence can be triggered by different starting conditions:
ALWAYS:
All starts (after controlled or uncontrolled stop, or after a power-up)
TRIP or POWER-UP: After uncontrolled stop, i.e. trip or coast, or after a power-up
TRIP:
After uncontrolled stop, i.e. trip or coast
The type of speed sequence may be Bidirectional or Unidirectional:
Bidirectional
Initially, the search is performed in the direction of the speed setpoint. If the drive fails
to identify the motor speed in this direction, a second speed search is performed in the
reverse direction.
Unidirectional
The search is performed only in the direction of the speed setpoint.
ACTIVE
Range: FALSE / TRUE
A diagnostic output indicating whether the flycatching sequence is active.
SETPOINT
Range xxx.xx %
This diagnostic output is the setpoint caught at the end of a successful flycatching sequence.
Содержание 605C
Страница 16: ...1 4 Getting Started 605C Frequency Inverter ...
Страница 22: ...2 6 An Overview of the Inverter 605C Frequency Inverter ...
Страница 50: ...4 14 Operating the Inverter 605C Frequency Inverter ...
Страница 66: ...5 16 The Operator Station 605C Frequency Inverter ...
Страница 156: ...8 2 Routine Maintenance and Repair 605C Frequency Inverter ...
Страница 184: ...10 22 Parameter Specification 605C Frequency Inverter ...
Страница 212: ...13 6 Application Notes 605C Frequency Inverter ...
Страница 214: ...14 2 Serial Communications 605C Frequency Inverter ...
Страница 236: ......