6-56
Programming Your Application
605C Frequency Inverter
REMOTE REVERSE
Range: FALSE / TRUE
For remote setpoints, setting this parameter TRUE inverts the demanded direction of motor
rotation.
REM TRIP RESET
Range: FALSE / TRUE
On a transition to TRUE, this input clears latched trips.
TRIP RST BY RUN
Range: FALSE / TRUE
This allows the rising edge of run command to clear latched trips.
POWER UP START
Range: FALSE / TRUE
If TRUE, this allows the Inverter to go directly to run mode if in remote and a run command is
present. If FALSE, a low to high transition of the run command is required.
TRIPPED
Range: FALSE / TRUE
Indicates that there is a latched trip present.
RUNNING
Range: FALSE / TRUE
Indicates that that the Inverter is in the enabled state.
JOGGING
Range: FALSE / TRUE
Indicates that the Inverter is in the JOG mode.
STOPPING
Range: FALSE / TRUE
Indicates that the Inverter is stopping.
OUTPUT CONTACTOR
Range: FALSE / TRUE
Output to be used to drive an external contactor in the motor output. This contactor is normally
closed unless a Trip condition has occurred or the Inverter goes into the re-configuration mode.
SWITCH ON ENABLE
Range: FALSE / TRUE
Sometimes referred to as READY TO SWITCH ON, this parameter indicates that the Inverter
will accept a run command.
SWITCHED ON
Range: FALSE / TRUE
Indicates that the Inverter’s power stack is operable and the Inverter will run if enabled.
READY
Range: FALSE / TRUE
Output indicating that the Inverter has accepted the run command.
SYSTEM RESET
Range: FALSE / TRUE
Output TRUE for a single cycle after the Inverter enters either RUN or JOG mode.
MAIN SEQ STATE
Range: Enumerated - see below
This parameter indicates the current sequencing state:
Enumerated Value
:
State
0 : NOT READY
1 : START DISABLED
2 : START ENABLED
3 : SWITCHED ON
4 : ENABLED
5 : F-STOP ACTIVE
6 : TRIP ACTIVE
7 : TRIPPED
REMOTE REV OUT
Range: FALSE / TRUE
This parameter indicates the current state of remote direction and RUN REV. Note - this is the
demanded direction, not the actual direction.
HEALTHY
Range: FALSE / TRUE
Set FALSE when the Inverter trips, and set TRUE when the run command is removed.
Содержание 605C
Страница 16: ...1 4 Getting Started 605C Frequency Inverter ...
Страница 22: ...2 6 An Overview of the Inverter 605C Frequency Inverter ...
Страница 50: ...4 14 Operating the Inverter 605C Frequency Inverter ...
Страница 66: ...5 16 The Operator Station 605C Frequency Inverter ...
Страница 156: ...8 2 Routine Maintenance and Repair 605C Frequency Inverter ...
Страница 184: ...10 22 Parameter Specification 605C Frequency Inverter ...
Страница 212: ...13 6 Application Notes 605C Frequency Inverter ...
Страница 214: ...14 2 Serial Communications 605C Frequency Inverter ...
Страница 236: ......