Programming Your Application
6-63
605C Frequency Inverter
STALL TRIP
The function block protects the motor from
damage that may be caused by continuous
operation beyond specification.
Functional Description
If the estimated load exceeds the STALL LIMIT for a time greater than STALL TIME then the
stall trip will become active. The timer is reset whenever the estimated load is less than the
STALL LIMIT.
Refer to Chapter 7 for a description of the trips supported by the Inverter.
MMI Menu Map
1
SETUP PARAMETERS
2
FUNCTION BLOCKS
3
TRIPS
4
STALL TRIP
STALL LIMIT
STALL TIME
STALL TRIP
100.00 % – [240] STALL LIMIT
–
600.0 s
–
[241] STALL TIME
–
Parameter Descriptions
STALL LIMIT
Range: 50.00 to 150.00 %
The load limit beyond which the stall trip monitoring becomes active.
STALL TIME
Range: 0.1 to 3000.0 s
The time after which a stall condition will cause a trip.