7-4
Trips and Fault Finding
605C Frequency Inverter
Checksum Fail
When the Inverter powers-up, non-volatile memory is checked to ensure that it has not been
corrupted. In the rare event of corruption being detected, the Inverter will not function. This
may occur when replacing the control board with an unprogrammed control board.
Inverter Indications
The failure is indicated by the HEALTH and RUN LEDs showing SHORT FLASH,
.
Referring to Chapter 4: “Operating the Inverter” - Reading the Status LEDs, you will note that
this also indicates Re-configuration mode, but this mode (and hence the indication) is not
available to the Inverter unless controlled by an MMI or Comms link.
Because you are controlling the Inverter locally (no MMI or Comms link etc.), the unit must be
returned to SSD Drives for reprogramming, refer to Chapter 8: “Routine Maintenance and
Repair” for address details. However, if you have access to an Operator Station or suitable PC
programming tool, the unit can be reset.
Operator Station Indications (when connected)
The MMI displays the message opposite.
Acknowledge the message by pressing the
E
key. This
action automatically loads and saves Macro 1 default
parameters and the ENGLISH 50Hz Product Code.
If your unit was using a different Product Code or macro,
you must reload the Product Code of your choice, reload
the macro of your choice, and perform a Parameter Save (SAVE/COMMAND menu) in that
order.
If data will not save correctly, the Operator Station will display a failure message. In this case,
the Inverter has developed a fault and must be returned to SSD Drives. Refer to Chapter 8:
“Routine Maintenance and Repair" for address details.
Fault Finding
Problem
Possible Cause
Remedy
Inverter will not power-up
Fuse blown
Check supply details, replace with
correct fuse.
Check Product Code against Model
No.
Faulty cabling
Check all connections are correct
and secure.
Check cable continuity
Inverter fuse keeps blowing
Faulty cabling or
connections wrong
Check for problem and rectify
before replacing with correct fuse
Faulty Inverter
Contact SSD Drives
Cannot obtain HEALTH state
Incorrect or no supply
available
Check supply details
Motor will not run at switch-on
Motor jammed
Stop the Inverter and clear the jam
Motor runs and stops
Motor becomes jammed
Stop the Inverter and clear the jam
Motor won’t rotate or runs in
reverse
Encoder fault
Check encoder connections
Open circuit speed
reference potentiometer
Check terminal
Table 7-2 Fault Finding
DEFAULT
HEALTH
LOCAL
SEQ
REF
1
1
DEFAULTS LOADED
* CHECKSUM FAIL*
Содержание 605C
Страница 16: ...1 4 Getting Started 605C Frequency Inverter ...
Страница 22: ...2 6 An Overview of the Inverter 605C Frequency Inverter ...
Страница 50: ...4 14 Operating the Inverter 605C Frequency Inverter ...
Страница 66: ...5 16 The Operator Station 605C Frequency Inverter ...
Страница 156: ...8 2 Routine Maintenance and Repair 605C Frequency Inverter ...
Страница 184: ...10 22 Parameter Specification 605C Frequency Inverter ...
Страница 212: ...13 6 Application Notes 605C Frequency Inverter ...
Страница 214: ...14 2 Serial Communications 605C Frequency Inverter ...
Страница 236: ......