Parameter Specification
10-7
605C Frequency Inverter
Tag
(MMI) Name
Block
Type
Range
ID
Notes
205
INPUT A
LOGIC FUNC 6
BOOL
FALSE / TRUE
5p
206
INPUT B
LOGIC FUNC 6
BOOL
FALSE / TRUE
5q
207
INPUT C
LOGIC FUNC 6
BOOL
FALSE / TRUE
5r
208
OUTPUT
LOGIC FUNC 6
BOOL
FALSE / TRUE
5s
Output
209
TYPE
LOGIC FUNC 6
ENUM
Same as tag 184
5t
210
INPUT A
LOGIC FUNC 7
BOOL
FALSE / TRUE
5u
211
INPUT B
LOGIC FUNC 7
BOOL
FALSE / TRUE
5v
212
INPUT C
LOGIC FUNC 7
BOOL
FALSE / TRUE
5w
213
OUTPUT
LOGIC FUNC 7
BOOL
FALSE / TRUE
5x
Output
214
TYPE
LOGIC FUNC 7
ENUM
Same as tag 184
5y
215
INPUT A
LOGIC FUNC 8
BOOL
FALSE / TRUE
5z
216
INPUT B
LOGIC FUNC 8
BOOL
FALSE / TRUE
60
217
INPUT C
LOGIC FUNC 8
BOOL
FALSE / TRUE
61
218
OUTPUT
LOGIC FUNC 8
BOOL
FALSE / TRUE
62
Output
219
TYPE
LOGIC FUNC 8
ENUM
Same as tag 184
63
220
INPUT A
LOGIC FUNC 9
BOOL
FALSE / TRUE
64
221
INPUT B
LOGIC FUNC 9
BOOL
FALSE / TRUE
65
222
INPUT C
LOGIC FUNC 9
BOOL
FALSE / TRUE
66
223
OUTPUT
LOGIC FUNC 9
BOOL
FALSE / TRUE
67
Output
224
TYPE
LOGIC FUNC 9
ENUM
Same as tag 184
68
225
INPUT A
LOGIC FUNC 10
BOOL
FALSE / TRUE
69
226
INPUT B
LOGIC FUNC 10
BOOL
FALSE / TRUE
6a
227
INPUT C
LOGIC FUNC 10
BOOL
FALSE / TRUE
6b
228
OUTPUT
LOGIC FUNC 10
BOOL
FALSE / TRUE
6c
Output
229
TYPE
LOGIC FUNC 10
ENUM
Same as tag 184
6d
230
OP VERSION
OP STATION
WORD
0000 to FFFF
6e
Output
231
DISABLED TRIPS
TRIPS STATUS
WORD
0000 to FFFF
6f
234
EXTERNAL TRIP
I/O TRIPS
BOOL
FALSE / TRUE
6i
1
235
INPUT 1 BREAK
I/O TRIPS
BOOL
FALSE / TRUE
6j
1
236
INPUT 2 BREAK
I/O TRIPS
BOOL
FALSE / TRUE
6k
1
237
I*T THRESHOLD
I*T TRIP
INT
50.00 to 105.00 %
6l
238
I*T TIME
I*T TRIP
USINT
5 to 60 s
6m
239
I*T UPPER LIMIT
I*T TRIP
INT
50.00 to 150.00 %
6n
240
STALL LIMIT
STALL TRIP
INT
50.00 to 150.00 %
6o
241
STALL TIME
STALL TRIP
INT
0.1 to 3000.0 s
6p
242
POWER FACTOR
CURRENT FEEDBACK
USINT
0.50 to 0.95
6q
3, 7
243
TRIM IN LOCAL
REFERENCE
BOOL
FALSE / TRUE
6r
244
RAMP TYPE
SYSTEM RAMP
ENUM
0 : LINEAR
1 : S
6s
245
REMOTE SETPOINT
REFERENCE
INT
-300.00 to 300.00 %
6t
246
JOG SETPOINT
JOG
INT
0.00 to 100.00 %
6u
247
LOCAL SETPOINT
REFERENCE
INT
0.00 to 100.00 %
6v
Output, 2
248
SPEED TRIM
REFERENCE
INT
-300.00 to 300.00 %
6w
249
REMOTE REVERSE
REFERENCE
BOOL
FALSE / TRUE
6x
250
LOCAL REVERSE
REFERENCE
BOOL
FALSE / TRUE
6y
Output, 2
252
MAX SPEED CLAMP
REFERENCE
INT
0.00 to 100.00 %
70
253
MIN SPEED CLAMP
REFERENCE
INT
-100.00 to 0.00 %
71
254
SPEED SETPOINT
REFERENCE
INT
xxx.xh % (h)
72
Output
Содержание 605C
Страница 16: ...1 4 Getting Started 605C Frequency Inverter ...
Страница 22: ...2 6 An Overview of the Inverter 605C Frequency Inverter ...
Страница 50: ...4 14 Operating the Inverter 605C Frequency Inverter ...
Страница 66: ...5 16 The Operator Station 605C Frequency Inverter ...
Страница 156: ...8 2 Routine Maintenance and Repair 605C Frequency Inverter ...
Страница 184: ...10 22 Parameter Specification 605C Frequency Inverter ...
Страница 212: ...13 6 Application Notes 605C Frequency Inverter ...
Страница 214: ...14 2 Serial Communications 605C Frequency Inverter ...
Страница 236: ......