12-4
Certification for the Inverter
605C Frequency Inverter
Single VSD -
Single Motor
Apply a single point
series earthing
strategy for a single
VSD mounted in a
cubicle as shown.
The protective earth
connection (PE) to
the motor must be
run inside the
screened cable
between the motor
and VSD and be
connected to the
motor protective
earth terminal on the
VSD.
Single VSD -
Multiple Motors
Note:
Refer to Chapter 13: “Application Notes” - Using Multiple Motors on a Single Drive.
If connecting multiple motors to a single VSD, use a star junction point for motor cable
connections. Use a metal box with entry and exit cable glands to maintain shield integrity.
Refer to Chapter 13: “Using Multiple Motors on a Single Inverter”.
605C
Back Panel
Cubicle
Motor
AC Supply
U-clip used to
terminate screen
connection to
the back panel
Armoured/screened cable
As short as possible
(0.3 metres maximum)
External
Filter
PE2 PE1
Additional PE connectors for
where PE1 is <10mm cross-section
2
Figure 12-1 EMC and Safety Earthing Cabling
Содержание 605C
Страница 16: ...1 4 Getting Started 605C Frequency Inverter ...
Страница 22: ...2 6 An Overview of the Inverter 605C Frequency Inverter ...
Страница 50: ...4 14 Operating the Inverter 605C Frequency Inverter ...
Страница 66: ...5 16 The Operator Station 605C Frequency Inverter ...
Страница 156: ...8 2 Routine Maintenance and Repair 605C Frequency Inverter ...
Страница 184: ...10 22 Parameter Specification 605C Frequency Inverter ...
Страница 212: ...13 6 Application Notes 605C Frequency Inverter ...
Страница 214: ...14 2 Serial Communications 605C Frequency Inverter ...
Страница 236: ......