Creating Custom Screens
You can create two “custom screens”, which can be
very useful when added to the OPERATOR menu.
Each screen contains:
•
a top line of sixteen characters
•
user-definable units
•
user-selectable scaling factor
•
user-selectable limits
•
user-selectable coefficients
This feature may be used to re-display the setpoint, for example, in more convenient units. Refer
to Chapter 6: “Programming Your Application” - CUSTOM SCREEN.
How to Save, Restore and Copy your Settings
Saving Your Application
The PARAMETER SAVE menu at level 1, only available in the Basic and Advanced view
levels, provides two save options:
1.
SAVE TO MEMORY menu at level 2:
saves to non-volatile memory within the Inverter
2.
SAVE TO OP menu at level 2:
saves to the Operator Station
Note:
The SAVE TO OP function produces a copy of the Inverter’s setup, including all user
options and the current password, refer to “Copying an Application” below.
Restoring Saved Settings
If you are unsure about any changes you have made,
you can re-load the last saved setup from memory.
Enter the LOAD FROM MEMORY menu at level 2 to
display the `UP` FOR ACTION page.
Note:
Pressing the
∆
key, as instructed, restores to the Inverter the last saved parameter
settings.
Copying an Application
The Operator Station is a programming tool for writing to the Inverter, where the information is
stored. But the Operator Station itself can also be used to store this data.
Transferring Your Application to Another Inverter
Note:
The Inverter you are copying to must have the same (or a newer software) release. Refer
to the Welcome screen (power-up).
1.
Write the application to the Operator Station via the SAVE TO OP menu at level 2. To
view the SAVE TO OP menu the Operator Station must have Basic or Advanced view level
selected.
2.
Connect the Operator Station to the receiving Inverter.
3.
Select Advanced view level, if necessary. Transfer the data via the LOAD FROM OP menu
at level 2. Two sub-menus allow you to choose between loading a full parameter load
which includes motor-specific data, or just the application without any motor-specific data:
ALL PARAMETERS
APPLICATION ONLY
Refer to Chapter 6: “Programming Your Application” - Motor-Specific Parameters.
HEALTH
LOCAL
SEQ
REF
1
1
103.0 l/s
WHISKY PUMPED
HEALTH
LOCAL
SEQ
REF
1
1
menu at level 2
LOAD FROM MEMORY
Содержание 605C
Страница 16: ...1 4 Getting Started 605C Frequency Inverter ...
Страница 22: ...2 6 An Overview of the Inverter 605C Frequency Inverter ...
Страница 50: ...4 14 Operating the Inverter 605C Frequency Inverter ...
Страница 66: ...5 16 The Operator Station 605C Frequency Inverter ...
Страница 156: ...8 2 Routine Maintenance and Repair 605C Frequency Inverter ...
Страница 184: ...10 22 Parameter Specification 605C Frequency Inverter ...
Страница 212: ...13 6 Application Notes 605C Frequency Inverter ...
Страница 214: ...14 2 Serial Communications 605C Frequency Inverter ...
Страница 236: ......