Parameter Specification
10-3
605C Frequency Inverter
Tag
(MMI) Name
Block
Type
Range
ID
Notes
28
FLY SETPOINT
FLY CATCHING
INT
xxx.xx %
0s
Output
30
DIN 1 INVERT
DIGITAL INPUT 1
BOOL
FALSE / TRUE
0u
31
DIN 1 VALUE
DIGITAL INPUT 1
BOOL
FALSE / TRUE
0v
Output
32
FLY SEARCH BOOST
FLY CATCHING
INT
0.00 to 100.00 %
0w
3
33
DIN 2 INVERT
DIGITAL INPUT 2
BOOL
FALSE / TRUE
0x
34
DIN 2 VALUE
DIGITAL INPUT 2
BOOL
FALSE / TRUE
0y
Output
36
DIN 3 INVERT
DIGITAL INPUT 3
BOOL
FALSE / TRUE
10
37
DIN 3 VALUE
DIGITAL INPUT 3
BOOL
FALSE / TRUE
11
Output
39
DIN 4 INVERT
DIGITAL INPUT 4
BOOL
FALSE / TRUE
13
40
DIN 4 VALUE
DIGITAL INPUT 4
BOOL
FALSE / TRUE
14
Output
42
DIN 5 INVERT
DIGITAL INPUT 5
BOOL
FALSE / TRUE
16
43
DIN 5 VALUE
DIGITAL INPUT 5
BOOL
FALSE / TRUE
17
Output
44
COEFFICIENT B
CUSTOM SCREEN 1
INT
1 to 30000
18
45
AOUT 1 VALUE
ANALOG OUTPUT 1
INT
-300.00 to 300.00 %
19
46
AOUT 1 SCALE
ANALOG OUTPUT 1
INT
-300.00 to 300.00 %
1a
47
AOUT 1 OFFSET
ANALOG OUTPUT 1
INT
-300.00 to 300.00 %
1b
48
AOUT 1 ABS
ANALOG OUTPUT 1
BOOL
FALSE / TRUE
1c
49
AOUT 1 TYPE
ANALOG OUTPUT 1
ENUM
0 : 0..+10 V
1 : 0..20 mA
2 : 4..20 mA
1d
7
50
QUADRATIC TORQUE
CURRENT FEEDBACK
BOOL
FALSE / TRUE
1e
5, 7
51
DOUT 1 INVERT
DIGITAL OUTPUT 1
BOOL
FALSE / TRUE
1f
52
DOUT 1 VALUE
DIGITAL OUTPUT 1
BOOL
FALSE / TRUE
1g
53
LOW LIMIT
CUSTOM SCREEN 1
INT
-30000 to 30000
1h
54
DOUT 2 INVERT
DIGITAL OUTPUT 2
BOOL
FALSE / TRUE
1i
55
DOUT 2 VALUE
DIGITAL OUTPUT 2
BOOL
FALSE / TRUE
1j
57
MAX SPEED
SETPOINT SCALE
INT
0.0 to 480.0 Hz
1l
7
58
SCALE INPUT
SETPOINT SCALE
INT
-300.00 to 300.00 %
1m
59
SCALE OUTPUT
SETPOINT SCALE
INT
xxx.xx %lf
1n
Output
60
SLEW ENABLE
SLEW RATE LIMIT
BOOL
FALSE / TRUE
1o
61
SLEW DECEL LIMIT
SLEW RATE LIMIT
INT
12.0 to 1200.0 Hz/s
1p
62
SLEW ACCEL LIMIT
SLEW RATE LIMIT
INT
12.0 to 1200.0 Hz/s
1q
64
FULL LOAD CALIB
CURRENT FEEDBACK
INT
0.0 to 1000.0 A
1s
3, 7
65
NO LOAD CALIB
CURRENT FEEDBACK
INT
0.0 to 1000.0 A
1t
3, 7
66
MOTOR CURRENT
CURRENT FEEDBACK
INT
xxx.xh % (h)
1u
Output
67
MOTOR CURRENT
CURRENT FEEDBACK
INT
xxxx.x A
1v
Output
68
I MAGNETISING
CURRENT FEEDBACK
INT
xxx.xh % (h)
1w
Output
69
I MAGNETISING
CURRENT FEEDBACK
INT
xxxx.x A
1x
Output
70
I TORQUE
CURRENT FEEDBACK
INT
xxx.xh % (h)
1y
Output
71
I TORQUE
CURRENT FEEDBACK
INT
xxxx.x A
1z
Output
72
LOAD
CURRENT FEEDBACK
INT
xxx.xh % (h)
20
Output
73
FIELD
CURRENT FEEDBACK
INT
xxx.xh % (h)
21
Output
74
TAG NO
CUSTOM SCREEN 1
TAG
0 to 787
22
75
DC LINK VOLTS
DYNAMIC BRAKING
INT
xxxx.x V
23
Output
77
BRAKE RESISTANCE
DYNAMIC BRAKING
INT
1 to 1000 Ohm
25
7
78
BRAKE POWER
DYNAMIC BRAKING
INT
0.1 to 510.0 kW
26
7
79
BRAKE 1S RATING
DYNAMIC BRAKING
INT
1 to 40
27
7
80
BRAKE ENABLE
DYNAMIC BRAKING
BOOL
FALSE / TRUE
28
81
BRAKING
DYNAMIC BRAKING
BOOL
FALSE / TRUE
29
Output
Содержание 605C
Страница 16: ...1 4 Getting Started 605C Frequency Inverter ...
Страница 22: ...2 6 An Overview of the Inverter 605C Frequency Inverter ...
Страница 50: ...4 14 Operating the Inverter 605C Frequency Inverter ...
Страница 66: ...5 16 The Operator Station 605C Frequency Inverter ...
Страница 156: ...8 2 Routine Maintenance and Repair 605C Frequency Inverter ...
Страница 184: ...10 22 Parameter Specification 605C Frequency Inverter ...
Страница 212: ...13 6 Application Notes 605C Frequency Inverter ...
Страница 214: ...14 2 Serial Communications 605C Frequency Inverter ...
Страница 236: ......