Application Macros
15-1
2
605C Frequency Inverter
Macro 5: Preset Speeds
Digital inputs select up to 8 preset speeds.
Additional Operator Menu display parameters.
Terminal
Name
Purpose
Comment
1
ANALOG INPUT 1
Setpoint
0V = 0%, 10V = 100%
2
ANALOG INPUT 2
Setpoint Trim
0V = 0%, 10V = 100%
6
ANALOG OUTPUT 1
Ramp Output
Absolute Speed Demand,
0V = 0%, 10V = 100%
13
DIGITAL INPUT 1
Run
24V = Run
14
DIGITAL INPUT 2
Trip Reset
0V to 24V transition to reset trips.
15
DIGITAL INPUT 3
Direction
0V = Forward, 24V = Reverse
16
DIGITAL INPUT 4
External Trip
0V = Trip
(connect to terminal 18)
17
DIGITAL INPUT 5
PID Enable
0V = PID Disabled,
24V = PID Enabled
18
DIGITAL INPUT 6
Preset 1
Preset Speed Select
19
DIGITAL INPUT 7
Preset 2
Preset Speed Select
20
DIGITAL INPUT 8
Preset 3
Preset Speed Select
21, 22
DIGITAL OUTPUT 1
Health
0V = Tripped, i.e. not healthy
23, 24
DIGITAL OUTPUT 2
Running
0V = Stopped, 24V = Running
The Operator Menu System for Macro 5
The default Operator menu system is shown below.
SETPOINT (REMOTE)
SPEED DEMAND
DRIVE FREQUENCY
MOTOR CURRENT
LOAD
PRESET 1 SELECT
PRESET 1 OUTPUT 1
PRESET 1 INPUT 0
STARTUP SCREEN
PRESET 1 INPUT 1
PRESET 1 INPUT 2
PRESET 1 INPUT 3
PRESET 1 INPUT 4
PRESET 1 INPUT 5
PRESET 1 INPUT 6
PRESET 1 INPUT 7
ENTER PASSWORD
Содержание 605C
Страница 16: ...1 4 Getting Started 605C Frequency Inverter ...
Страница 22: ...2 6 An Overview of the Inverter 605C Frequency Inverter ...
Страница 50: ...4 14 Operating the Inverter 605C Frequency Inverter ...
Страница 66: ...5 16 The Operator Station 605C Frequency Inverter ...
Страница 156: ...8 2 Routine Maintenance and Repair 605C Frequency Inverter ...
Страница 184: ...10 22 Parameter Specification 605C Frequency Inverter ...
Страница 212: ...13 6 Application Notes 605C Frequency Inverter ...
Страница 214: ...14 2 Serial Communications 605C Frequency Inverter ...
Страница 236: ......