Programming Your Application
6-45
605C Frequency Inverter
AUTO BACKUP
Range: FALSE / TRUE
When this input is set to TRUE, performing a SAVE TO MEMORY function block operation
also saves the configuration of the Inverter to the connected Operator Station.
CONFIGURATION ID
Range: 16
characters
This 16 character string is displayed as the top line of the Welcome screen.
OP DATABASE
Range: FALSE / TRUE
When TRUE, this diagnostic output indicates that the connected Operator Station contains a
configuration that may be loaded into the Inverter.
OP VERSION
Range: 0000
to FFFF
Displays the software version of the Operator Station. It is cleared to 0000 if no Operator
Station is connected.