• The unit must not share the chimney with other equipment.
• Pipes outside the operating area must have double stainless-steel insulation and an
internal diameter of 80 mm (Hidro 12) or 100 mm (Hidro 17 and Hidro 23).
•
The fume exhaust pipe may generate condensation, so we recommend that
the appropriate systems for collecting condensates should be installed.
5.3.
Installation without a chimney
The installation of the free-standing pellet fire without a chimney should be performed
as illustrated in Figure 10, equipped with an exhaust pipe (with a minimum diameter
of 80 mm for the
Hidro 12
and 100 mm for the
Hidro 17
and
Hidro 23
model)
directly outside and over the roof.
Double-walled stainless steel insulated pipes must be used and properly fastened to
avoid condensation.
A T-tube must be installed at the base of the pipe to allow periodic inspections and
annual maintenance, as illustrated in Figure 10.
Figure 10 - Side view of the installation without a chimney, illustrating the inspection point