Draught in the chimney:
The figures below show three standard diagrams,
specifying adequate lengths and diameters. Any other type of installation must
guarantee a draught of 12 Pa (0,12 mbars) measured when hot and at the maximum
power.
Ventilation:
To get the optimum operation of the unit it
is necessary that the
installation location has an air inlet with a minimum section of 100 cm
2
,
preferably near the back panel of the unit.
The free-standing pellet fire unit has a
circular pipe (
50mm) that may be connected to the exterior of the house.
If the residence has an air exhaust system installed (e.g., kitchen extractor
fan), a top ventilation section must be installed, suitable to accommodate the
different air exhaust units’ systems that exist in the house.
The installation of the unit on locations near kitchen exhaust fans or fume
extractors may prevent the unit from operating properly.
5.4.
Installation with a chimney
As shown in Figure 12, the unit is installed with an exhaust pipe (
80 mm for the
Hidro 12
;
100 mm for the
Hidro 17
and
Hidro 23
) directly on to the chimney. If
the chimney is too large, an 80 mm-wide pipe should be installed at the fume outlet.
A T-tube must be attached to the base of the pipe to allow for periodic inspection and
annual maintenance, as illustrated in Figure 12.
Содержание Hidro 12
Страница 18: ...12 Figure 11 specifies the basic requirements for installing the chimney to the unit a b ...
Страница 102: ...96 ...
Страница 103: ...97 ...
Страница 104: ...98 ...
Страница 133: ...127 25 2 Flow chart Hidro 12 Flow chart 1 Lighting ...
Страница 134: ...128 ...
Страница 135: ...129 Flow chart 2 Disabling Note The circulator pump off below 40 C water temperature ...
Страница 136: ...130 25 3 Flow chart Hidro 17 and Hidro 23 Flow chart 1 Lighting ...
Страница 137: ...131 ...
Страница 138: ...132 Flow chart 2 Disabling Note The circulator pump off below 40 C water temperature ...