HGM9520N Genset Paralleled Controller User Manual Page 25 of 111
No
Type
Description
power (negative) is above the preset limit, it shall issue a block alarm.
It is always detected.
14
ECU Alarm
When the controller receives the engine alarm signal from J1939, it
shall issue a block alarm.
It is always detected.
15
Temp. Sensor Open
When the controller detects the sensor circuit is open, it shall issue a
block alarm.
It is always detected.
16
Engine Temp High
When this is enabled, and the controller detects the temp. is above the
preset limit, it shall issue a block alarm.
It is detected after “safety on time” before “ETS solenoid hold”.
17
Engine Temp Low
When this is enabled, and the controller detects the temp. is below the
preset limit, it shall issue a block alarm.
It is detected after “safety on time” before “ETS solenoid hold”.
18
Oil Pressure Sensor
Open
When the controller detects the sensor circuit is open, it shall issue a
block alarm.
It is always detected.
19
Oil Pressure Low
When this is enabled, and the controller detects the pressure is below
the preset limit, it shall issue a block alarm.
It is detected after “safety on time” before “ETS solenoid hold”.
20
Oil Pressure Sensor
Wrong
When voltage or current input is selected for the curve type of the
controller, and the controller detects input signal is abnormal, it shall
issue a block alarm, and meanwhile the curve is transferred to resistor
type to prevent damaging the controller.
It is detected always.
21
Fuel Level Sensor Open
When the controller detects the sensor circuit is open, it shall issue a
block alarm.
It is always detected.
22
Fuel Level Low
When this is enabled, and the controller detects the level is below the
preset limit, it shall issue a block alarm.
It is always detected.
23
Flex. Sensor 1 Open
When the controller detects the sensor circuit is open, it shall issue a
block alarm.
It is always detected.
24
Flex. Sensor 1 High
When over high block alarm is enabled, and the controller detects the
sensor value is above the preset upper limit, it shall issue a block alarm.
It is detected after “safety on time” before “ETS solenoid hold” when the
sensor is selected as temperature sensor and pressure sensor;
It is always detected when the sensor is selected as fuel level sensor.
25
Flex. Sensor 1 Low
When over low block alarm is enabled, and the controller detects the
sensor value is below the preset low limit, it shall issue a block alarm.
It is detected after “safety on time” before “ETS solenoid hold” when the
sensor is selected as temperature sensor and pressure sensor;