HGM9520N Genset Paralleled Controller User Manual Page 64 of 111
No.
Items
Parameters
Defaults
Description
(0~7)
1
Action
28.
Earth Fault 2
(0~1)
(0~200.0)%
(0~200.0)%
(0~3600)s
(0~7)
0
20.0
18.0
5
0
0: Disable 1: Enable
Set value is percentage of rated current.
Return value is percentage of rated current.
Delay value
Action
29.
Rated Power(W)
(0~6000)kW
276
Genset rated active power, which is
standard of loading active power.
30.
Rated Power(var)
(0~6000)kvar
210
Genset rated reactive power, which is
standard of loading reactive power.
31.
Load Ramp Rate
(0.1~100.0)%/s
3.0
For each time of genset loads the set ramp
point power, after the set ramp delay time, it
will upload to the target power by the set
ramp rate.
32.
Load Ramp Point
(0.1~40.0)%
10.0
33.
Load Ramp Delay
(0~30)s
0
34.
Unload Ramp Rate
(0.1~100.0)%/s
3.0
Genset unloading speed
35.
Over Power 1 Set
(0~1)
(0~200.0)%
(0~200.0)%
(0~3600)s
(0~7)
1
120.0
118.0
3
6
0: Disable 1: Enable
Set value is percentage of gen rated active
power.
Return value is percentage of gen rated
active power.
Delay value
Action
36.
Over Power 2 Set
(0~1)
(0~200.0)%
(0~200.0)%
(0~3600)s
(0~7)
1
110.0
108.0
5
1
0: Disable 1: Enable
Set value is percentage of gen rated active
power.
Return value is percentage of gen rated
active power.
Delay value
Action
37.
Reverse Power 1
Set
(0~1)
(0~200.0)%
(0~200.0)%
(0~3600)s
(0~7)
1
10.0
8.0
3
7
0: Disable 1: Enable
Set value is percentage of gen rated active
power.
Return value is percentage of gen rated
active power.
Delay value
Action
38.
Reverse Power 2
Set
(0~1)
(0~200.0)%
(0~200.0)%
(0~3600)s
(0~7)
1
5.0
3.0
5
1
0: Disable 1: Enable
Set value is percentage of gen rated active
power.
Return value is percentage of gen rated
active power.
Delay value
Action