HGM9520N Genset Paralleled Controller User Manual Page 86 of 111
No.
Type
Description
25
Reserved
26
Aux. High Temp
Connected sensor digital input.
27
Aux. Low OP
Connected sensor digital input.
28
Remote Start
(On Load)
In
Auto
mode, when input is active, genset can start automatically
and take load after genset is OK; when input is inactive, genset will
stop automatically.
29
Remote Start
(Off Load)
In
Auto
mode, when input is active, genset can start automatically
and won't take load after genset is OK; when input is inactive, genset
will stop automatically.
30
Aux. Manual Start
In
Manual
mode, when input is active, genset will start automatically;
when input is inactive, genset will stop automatically
31
Remote Start
(On Demand)
In
Auto
mode, when input is active, all gensets that need to be
paralleled will start according to the priority and call other generators
according to the load.
32
Remote Start (Island)
In
Auto
mode, when input is active, genset can start automatically
and take load when gen is Ok; Mains takes off load. When input is
inactive, Mains takes load, Gen takes off load, genset stops
automatically.
33
Simulate Stop key
An external button (Not Self-locking) can be connected and pressed
as simulate panel button.
34
Simulate Manual key
35
Reserved
36
Simulate Auto key
An external button (Not Self-locking) can be connected and pressed
as simulate panel button.
37
Simulate Start key
38
Simulate G-Load key
39
Simulate M-Load key
40
NEL Manual Trip
An external button (Not Self-locking) can be connected. Details of
function description please see the following.
41
NEL Manual
Re-connection
42
Power Manager Mode
Power management mode will be displayed on the LCD when the
input is active. In this mode, the controller will control genset
synchronization, power sharing, scheduled start/stop, breaker
open/close.
Details of function description please see the following.
43
Mains Parallel Mode
Not available for HGM9520N.
44
First Priority
Not available for HGM9520N.
45-4
6
Reserved
47
Alternative Config 1
When input is active, alternative configuration is active. Users can set
different parameters to make it easy to select current configuration
via input port.
48
Alternative Config 2
49
Alternative Config 3
50
Balance Test
Not available for HGM9520N.
51
Speed Raise