HGM9520N Genset Paralleled Controller User Manual Page 32 of 111
No
Type
Description
38
DIN16 Input Alarm
When DIN16 input is set users-defined and if it is active, the controller
will initiate an alarm signal.
It is detected in the detection range set in the input.
39
DOUT16 Comm. Fail
When DOUT16 communication is enabled and the controller cannot
receive the communication data, it will initiate an alarm signal.
It is always detected.
40
AIN24 Comm. Fail
When AIN24 communication is enabled and the controller cannot
receive the communication data, it will initiate an alarm signal.
It is always detected.
41
AIN24 Cylinder Temp.
High
When this is enabled and the controller detects cylinder temperature
has exceeded the pre-set value, it will initiate an alarm signal.
It is detected after “safety on time” before “ETS solenoid hold”.
42
AIN24 Exhaust Temp.
High
When this is enabled and the controller detects exhaust temperature
has exceeded the pre-set value, it will initiate an alarm signal.
It is detected after “safety on time” before “ETS solenoid hold”.
43
AIN24 Cylinder Temp.
Difference High
When this is enabled and the controller detects cylinder temp.
difference has exceeded the pre-set value, it will initiate an alarm signal.
It is detected after “safety on time” before “ETS solenoid hold”.
44
AIN24 Sensor Open
When the controller detects the sensor circuit is open, it shall issue an
alarm signal.
It is always detected.
45
AIN24 Sensor High
When over high alarm is enabled, and the controller detects the sensor
value is above the preset upper limit, it shall issue an alarm signal.
It is detected after “safety on time” before “ETS solenoid hold” when the
sensor is selected as temperature sensor and pressure sensor;
It is always detected when the sensor is selected as fuel level sensor.
46
AIN24 Sensor Low
When over low alarm is enabled, and the controller detects the sensor
value is below the preset lower limit, it shall issue an alarm signal.
It is detected after “safety on time” before “ETS solenoid hold” when the
sensor is selected as temperature sensor and pressure sensor;
It is always detected when the sensor is selected as fuel level sensor.
47
AIN8 Comm. Fail
When AIN8 communication is enabled and the controller cannot receive
the communication data, it will initiate an alarm signal.
It is always detected.
48
AIN8 Sensor Open
When the controller detects the sensor circuit is open, it shall issue an
alarm signal.
It is always detected.
49
AIN8 Sensor High
When over high alarm is enabled, and the controller detects the sensor
value is above the preset upper limit, it shall issue an alarm signal.
It is detected after “safety on time” before “ETS solenoid hold” when the
sensor is selected as temperature sensor and pressure sensor;
It is always detected when the sensor is selected as fuel level sensor.
50
AIN8 Sensor Low
When over low alarm is enabled, and the controller detects the sensor