HGM9520N Genset Paralleled Controller User Manual Page 84 of 111
7.2.2
DEFINED PERIOD OUTPUT
Defined period output is composed by 2 parts,
period output S1
and
condition output S2.
While
S1
and
S2
are
TRUE
synchronously, OUTPUT;
While
S1
or
S2
is
FALSE
, NOT OUTPUT.
Period output S1
can be set to generator’s one or more period output freely, the delayed output time
and output time after enter into period can also be configured.
Condition output S2
can set as any contents in output ports.
NOTE:
when delay time and output time both are 0 in period output S1, it is TRUE in this period.
Output period: start
Delay output time: 2s
Output time: 3s
Condition output contents: output port 1 is active
Close when condition output active/inactive: close when active (disconnect when inactive);
Output port 1 active, after enter “starts time” and delay 2s, this defined period output is outputting, after 3s, stop
outputting;
Output port 1 inactive, defined output period is not outputting.
7.2.3
DEFINED COMBINATION OUTPUT
Defined combination output is composed by 3 parts,
or
condition output S1, or
condition output S2
,
and condition output S3
.
S1 or S2 is
TRUE
, while S3 is
TRUE
, defined combination output is outputting;
S1 and S2 are
FALSE
, or S3 is
FALSE
, defined combination output is not outputting.
NOTE:
S1, S2, S3 can be set as any contents except for “defined combination output” in the output setting.
NOTE:
3 parts of defined combination output (S1, S2, S3) couldn’t include or recursively include themselves.
For example:
Contents of or condition output S1: output port 1 is active;
Close when or condition output S1 is active /inactive: close when active (disconnect when inactive);
Contents of or condition output S2, output port 2 is active;
Close when or condition output S2 is active /inactive: close when active (disconnect when inactive);
Contents of and condition output S3: output port 3 is active;
Close when and condition output S3 is active /inactive: close when active (disconnect when inactive);
When input port 1 active or input port 2 active, if input port 3 is active, defined combination output is outputting; If input
port 3 inactive, defined combination output is not outputting;
When input port 1 inactive and input port 2 inactive, whatever input port 3 is active or not, defined combination output is
not outputting.