HGM9520N Genset Paralleled Controller User Manual Page 67 of 111
No.
Items
Parameters
Defaults
Description
1.
Contents Setting
(0~70)
26
High temperature shutdown input
2.
Active Type
(0~1)
0
0: Close 1: Open
Digital Input Port 4
1.
Contents Setting
(0~70)
13
Gen close status input
2.
Active Type
(0~1)
0
0: Close 1: Open
Digital Input Port 5
1.
Contents Setting
(0~70)
0
Users-defined
2.
Active Type
(0~1)
0
0: Closed to active
1: Open to active
3.
Arming
(0~3)
3
0: From safety on 1: From starting
2: Always 3: Never
4.
Active Actions
(0~7)
4
0: None; 1: Warning; 2: Block; 3: Safety Trip;
4: Safety Trip and Stop; 5: Trip; 6: Trip and
Stop; 7: Shutdown.
5.
Active Delay
(0~20.0)s
2.0
Time from detecting active to confirm
6.
Description
LCD displays detailed contents when the
input is active.
Digital Input Port 6
1.
Contents Setting
(0~70)
44
Master choice
2.
Active Type
(0~1)
0
0: Close 1: Open
Digital Input Port 7
1.
Contents Setting
(0~70)
0
Users-defined.
2.
Active Type
(0~1)
0
0: Close 1: Open
3.
Arming
(0~3)
3
0: From safety on 1: From starting
2: Always 3: Never
4.
Active Actions
(0~7)
4
0: None; 1: Warning; 2: Block; 3: Safety Trip;
4: Safety Trip and Stop; 5: Trip; 6: Trip and
Stop; 7: Shutdown.
5.
Active Delay
(0~20.0)s
2.0
Time from detecting active to confirm
6.
Description
LCD displays detailed contents when the
input is active.
Digital Input Port 8
1.
Contents Setting
(0~70)
0
User defined.
2.
Active Type
(0~1)
0
0: Close 1: Open
3.
Arming
(0~3)
3
0: From safety on 1: From starting
2: Always 3: Never
4.
Active Actions
(0~7)
4
0: None; 1: Warning; 2: Block; 3: Safety Trip;
4: Safety Trip and Stop; 5: Trip; 6: Trip and
Stop; 7: Shutdown.
5.
Active Delay
(0~20.0)s
2.0
Time from detecting active to confirm
6.
Description
LCD displays detailed contents when the
input is active.