HGM9520N Genset Paralleled Controller User Manual Page 29 of 111
5.3
SAFETY TRIP
When controller detects safety trip signals, it will open breaker after soft unloading but not stop the
genset. Users need to reset alarms manually.
Table 10 Safety Trip
No
Type
Description
1
Over Speed
When this is enabled, and the controller detects that the genset speed
is above the pre-set limit, it will initiate an alarm signal.
It is always detected.
2
Under Speed
When this is enabled and the controller detects that the genset speed is
below the pre-set limit, it will initiate an alarm signal.
It is detected after “warming up” and before “stop idle”.
3
Loss of Speed Signal
When the controller detects the genset speed is 0, it shall issue an
alarm signal.
It is detected after “safety on time” and before “ETS solenoid hold”.
4
Gen Over Frequency
When this is enabled, and the controller detects the genset frequency is
above preset limit, it shall issue an alarm signal.
It is detected always.
5
Gen Under Frequency
When this is enabled, and the controller detects the frequency is below
the preset limit, it shall issue an alarm signal.
It is detected after “warming up” and before “stop idle”.
6
Gen Over Voltage
When this is enabled, and the controller detects the genset voltage is
above preset limit, it shall issue an alarm signal.
It is detected always.
7
Gen Under Voltage
When this is enabled, and the controller detects the voltage is below the
preset limit, it shall issue an alarm signal.
It is detected after “warming up” and before “stop idle”.
8
Gen Over Current
When this is enabled, and the controller detects the genset current is
above preset limit, it shall issue an alarm signal.
It is detected always.
9
Negative Sequence
Current
When this is enabled, and the controller detects the unbalanced current
is above preset limit, it shall issue an alarm signal.
It is detected always.
10
Earth Fault
When this is enabled, and the controller detects the earth current is
above the preset limit, it shall issue an alarm signal.
It is always detected.
11
Reverse Power
When this is enabled, and the controller detects the reverse power
(negative) is above the preset limit, it shall issue an alarm signal.
It is always detected.
12
Over Power
When this is enabled, and the controller detects the genset power
(positive) is above the preset limit, it shall issue an alarm signal.
It is always detected.
13
Loss Excitation
When this is enabled, and the controller detects the genset reactive