HGM9520N Genset Paralleled Controller User Manual Page 57 of 111
7
SCOPES AND DEFINITIONS OF PROGRAMMABLE PARAMETERS
7.1
CONTENTS AND SCOPES OF PARAMETERS
Table 16 Parameter Configuration
No.
Items
Parameters
Defaults
Description
Module Setting
1.
Power On Mode
(0~2)
0
0: Stop Mode
1: Manual Mode
2: Auto Mode
2.
Communication
Address
(1~254)
1
Controller address for remote monitoring.
3.
Communication
Stop Bit
(0~1)
0
0: 2-Bit Stop Bit
1: 1-Bit Stop Bit
This cannot be set on the front panel.
4.
Language
(0~2)
0
0: Simplified Chinese
1: English
2: Other
5.
Password
(0~65535)
00318
It is used to enter advanced parameter
setting.
6.
Daylight Saving
Time
(0~1)
0
0: Disable
1: Enable
Start and end time for this can be set.
7.
Date and Time
It is used for date and time settings.
8.
Temperature Unit
(0~1)
0
0:
℃
; 1:
℉
9.
Pressure Unit
(0~2)
0
0: kPa; 1: psi; 2: bar
10.
Backlight Time
(0~3600)s
300
11.
Non-parallel Mode
(0~1)
0
0: Disable 1: Enable
12.
Network
(0~1)
1
0: Disable 1: Enable
13.
J1939-75
(0~1)
0
0: Disable 1: Enable
14.
Alarm Data Interval (0~60.0)s
0.1
15.
MSC2
(0~1)
0
0: Disable 1: Enable
When it is enabled, MSC1 works with MSC2
in parallel.
(Not available for HGM9520N)
16.
Mains/Redundant
(0~2)
0
0: Sole Module
1: Main Module
2: Redundant Module
(Not available for HGM9520N)
17.
Fn Function
(0~6)
0
0: Fn Button
1: Stop Button
2: Start Button
3: Manual Button
4: Auto Button