HGM9520N Genset Paralleled Controller User Manual Page 13 of 111
NOTE
: Press
and
simultaneously in manual mode and it can force the generator to crank. At this time
the controller shall not judge whether the genset start is successful or not according to the starting conditions. It is
controlled by the operator. When operator observes that the engine has started, he/she should release the button and the
start output will be deactivated. Safety on delay will be initiated.
NOTE:
Regarding ECU genset, in Stop/Auto mode, Press
button and it shall power on the ECU (fuel output
and ECU power output are active.).
CAUTION:
Factory default password is “00318”, and users can change it in case others change the advanced
parameter settings. Please clearly remember the password after changing. If you forget it, please contact SmartGen
services and send the PD information in the controller page of “
ABOUT
” to the service personnel.
4.3
LCD DISPLAY
4.3.1
MAIN DISPLAY
Paging is applied for the main screen;
is used for page scroll and
for screen scroll.
Main Screen
includes the following contents:
Gen: voltage, frequency, current, active power, reactive power;
Mains: voltage, frequency;
Engine: speed, temperature, engine oil pressure, battery voltage;
Part of status displays;
Status
page includes the following contents:
Genset status, Mains status and ATS status;
Engine
page includes the following contents:
Engine speed, engine temperature, engine oil pressure, fuel level, configurable analog 1, configurable
analog 2, battery voltage, charger voltage, accumulated running time, accumulated start times.
NOTE:
If CAN BUS is connected and engine information is from J1939, this page also includes: coolant pressure,
coolant level, fuel temperature, fuel pressure, inlet temperature, exhaust temperature, turbo pressure, fuel consumption,
total fuel consumption and so on. (Different engines have different parameters.)
Generator
page includes the following contents:
Phase voltage, wire voltage, frequency, phase sequence, current, active power of different phases, total
active power and percentage, reactive power of different phases, total reactive power and percentage,
apparent power of different phases, total apparent power, power factor of different phases, average
power factor, accumulated electric power, total power of multi-genset; ground current and percentage,
unbalance current and percentage, unbalance voltage and percentage.
NOTE:
NOTE:
P stands for active power;
Q stands for reactive power.
Fig. 2 Power Factor Display Description