HGM9520N Genset Paralleled Controller User Manual Page 63 of 111
No.
Items
Parameters
Defaults
Description
18.
Volt Unbalance 2
(0~1)
(0~200.0)%
(0~200.0)%
(0~3600)s
(0~7)
0
10.0
5.0
5
0
0: Disable 1: Enable
Set value is gen degree of unbalance.
Return value is gen degree of unbalance.
Delay value
Action
19.
THD Alarm 1
(0~1)
(0~200.0)%
(0~200.0)%
(0~3600)s
(0~7)
0
10.0
5.0
5
0
0: Disable 1: Enable
Set value is gen degree of distortion.
Return value is gen degree of distortion.
Delay value
Action
20.
THD Alarm 2
(0~1)
(0~200.0)%
(0~200.0)%
(0~3600)s
(0~7)
0
10.0
5.0
5
0
0: Disable 1: Enable
Set value is gen degree of distortion.
Return value is gen degree of distortion.
Delay value
Action
21.
CT
(5~6000)/5
500
Ratio of external connected current
transformer.
22.
Rated Current
(5~6000)A
500
It is rated current of generator and used for
loading current standard.
23.
Over Current 1
(0~1)
(0~200.0)%
(0~200.0)%
(0~3600)s
(0~7)
1
120.0
118.0
3
6
0: Disable 1: Enable
Set value is percentage of rated current.
Return value is percentage of rated current.
Delay value
Action
24.
Over Current 2
(0~1)
(0~200.0)%
(0~200.0)%
(0~3600)s
(0~7)
1
110.0
108.0
5
1
0: Disable 1: Enable
Set value is percentage of rated current.
Return value is percentage of rated current.
Delay value
Action
25.
NegSeq Current 1
(0~1)
(0~200.0)%
(0~200.0)%
(0~3600)s
(0~7)
1
20.0
18.0
5
1
0: Disable 1: Enable
Set value is percentage of rated current.
Return value is percentage of rated current.
Delay value
Action
26.
NegSeq Current 2
(0~1)
(0~200.0)%
(0~200.0)%
(0~3600)s
(0~7)
0
20.0
18.0
5
0
0: Disable 1: Enable
Set value is percentage of rated current.
Return value is percentage of rated current.
Delay value
Action
27.
Earth Fault 1
(0~1)
(0~200.0)%
(0~200.0)%
(0~3600)s
1
20.0
18.0
5
0: Disable 1: Enable
Set value is percentage of rated current.
Return value is percentage of rated current.
Delay value