HGM9520N Genset Paralleled Controller User Manual Page 75 of 111
No.
Items
Parameters
Defaults
Description
6.
Export Power Opt
(0~1)
0
0: kvar Reactive Power Control;
1: PF Power Factor Control.
7.
Export Power (var)
(0~100.0)%
8.0
It is used to load control.
8.
Analogue Adjust
(W)
(0~1)
0
0: Disable; 1: Enable.
When it is enabled, flexible sensor 1 is used
as analog input.
It is active when active power output mode
is configured as Fixed Power.
9.
Analogue Adjust
(var)
(0~1)
0
0: Disable; 1: Enable.
When it is enabled, flexible sensor 2 is used
as analog input.
It is active when reactive power output
mode is configured as Fixed Power.
10.
Export Curve (W)
Configure gen frequency-active power
curve.
It is active when active power output mode
is configured as Frequency-Power.
11.
Export Curve (var)
Configure gen voltage-reactive power
curve.
It is active when active power output mode
is configured as Voltage-Power.
GOV/AVR
1.
GOV SW1
(0~20.00)
0
Center voltage, default 0V.
2.
GOV SW2
(0~10.00)
2.00
Voltage range, default (-2.5~+2.5V).
3.
AVR SW1
(0~20.00)
0
Center voltage, default 0V.
4.
AVR SW2
(0~10.00)
2.0
Voltage range, default (-2.5~+2.5V).
Mains Setting
1.
AC System
(0~3)
0
0: 3P4W; 1: 3P3W;
2: 2P3W; 3: 1P2W.
2.
Rated Voltage
(30~30000)V
230
Offer standards for detecting mains’
over/under voltage. (It is primary voltage
when voltage transformer is used; it is line
voltage when AC system is 3P3W while it is
phase voltage when other AC system is
used.
3.
Mains Rated
Frequency
(10.0~75.0)Hz
50.0
Offer standards for detecting over/under
frequency.
4.
Volt. Trans.(PT)
(0~1)
0
0: Disable ; 1: Enable
5.
Mains Split Action
(0~1)
0
0: Trip and Stop; 1: Aux. Mains Fail.
6.
Mains Over Voltage
(0~1)
(0~200.0)%
(0~20.0)s
1
110.0
0.1
Set value is percentage of mains rated volt.
7.
Mains
Under (0~1)
1