DEFINED CONTENTS OF DIGITAL INPUT PORTS
Table 18 Definition of Digital Input Ports
No.
Type
Description
0
Users Configured
Users-defined alarm.
Active range:
Never: input inactive.
Always: input is active all the time.
From crank: detecting as soon as start.
From safety on: detecting after safety on run delay.
1
Reserved
2
Alarm Mute
Can prohibit ‘Audible Alarm’ output when input is active.
3
Reset Alarm
Can reset shutdown alarm and trip alarm when input is active.
4
60Hz Active
Use for CANBUS ECU engine and it is 60Hz when input is active.
5
Lamp Test
All LED indicators are illuminated when input is active.
6
Panel Lock
All buttons on panel are inactive except navigation buttons and there
is in the right top corner on LCD when input is active.
7
Redundancy Active
Not available for HGM9520N.
8
Idle Control Mode
Under voltage/frequency/speed protection is inactive.
9
Inhibit Auto Stop
In
Auto
mode, during generator normal running, when input is active,
prohibit generator shutdown automatically.
10
Inhibit Auto Start
In
Auto
mode, prohibit generator start automatically when input is
active.
11
Inhibit Scheduled Start
In
Auto
mode, prohibit fixed timing start genset when input is active.
12
Gen Close Inhibit
When input is active and “Gen Close” needs to be outputted, “Gen
Close” process will wait and will not close genset.
13
Gen Closed Input
Connect generator loading switch’s auxiliary point.
14
Inhibit Gen Load
Prohibit genset to take load when input is active, and gen close
process won't be conducted.
15
Mains Closed Input
Connect Mains loading switch's auxiliary point.
16
Inhibit Mains Load
Prohibit Mains to take load when input is active, and Mains close
process won't be conducted.
17
Auto Mode Input
When input is active, controller enters into Auto mode.
18
Auto Mode Inhibit
When input is active, controller won’t work under Auto mode. Auto
key and simulate auto key inputs do not work.
19
Static Parallel
Not available for HGM9520N.
20
Black Start Input
Not available for HGM9520N.
21
Inhibit Alarm Stop
All shutdown alarms are prohibited except emergence stop.(Means
battle mode)
22
Instrument Mode
All outputs are prohibited in this mode.
23
Non-Parallel Mode
No parallel process when load is transferred under this mode.
24
Reset Maintenance
Controller will set maintenance time and date as default when input is
active.