HGM9520N Genset Paralleled Controller User Manual Page 68 of 111
No.
Items
Parameters
Defaults
Description
Digital Input Port 9
1.
Contents Setting
(0~70)
0
Users-defined
2.
Active Type
(0~1)
0
0: Close 1: Open
3.
Arming
(0~3)
3
0: From safety on 1: From starting
2: Always 3: Never
4.
Active Actions
(0~7)
4
0: None; 1: Warning; 2: Block; 3: Safety Trip;
4: Safety Trip and Stop; 5: Trip; 6: Trip and
Stop; 7: Shutdown.
5.
Active Delay
(0~20.0)s
2.0
Time from detecting active to confirm
6.
Description
LCD displays detailed contents when the
input is active.
Digital Input Port 10
1.
Contents Setting
(0~70)
0
Users-defined
2.
Active Type
(0~1)
0
0: Close 1: Open
3.
Arming
(0~3)
3
0: From safety on 1: From starting
2: Always 3: Never
4.
Active Actions
(0~7)
4
0: None; 1: Warning; 2: Block; 3: Safety Trip;
4: Safety Trip and Stop; 5: Trip; 6: Trip and
Stop; 7: Shutdown.
5.
Active Delay
(0~20.0)s
2.0
Time from detecting active to confirm
6.
Description
LCD displays detailed contents when the
input is active.
Digital Output Ports
Digital Output Port 1
1
Contents Setting
(0~299)
44
Normal generating output.
2
Active Type
(0~1)
0
0: Normally open; 1: Normally close
Digital Output Port 2
1
Contents Setting
(0~299)
48
Common Alarm.
2
Active Type
(0~1)
0
0: Normally open; 1: Normally close
Digital Output Port 3
1
Contents Setting
(0~299)
38
Energize to Stop.
2
Active Type
(0~1)
0
0: Normally open; 1: Normally close
Digital Output Port 4
1
Contents Setting
(0~299)
35
Idle Control.
2
Active Type
(0~1)
0
0: Normally open; 1: Normally close
Digital Output Port 5
1
Contents Setting
(0~299)
30
Open Gen Output.
2
Active Type
(0~1)
0
0: Normally open; 1: Normally close
Digital Output Port 6
1
Contents Setting
(0~299)
29
Close Gen Output.
2
Active Type
(0~1)
0
0: Normally open; 1: Normally close
Digital Output Port 7