User Manual
EM303A General Purpose Inverter
95
In torque control mode, if the function terminal is on, then the special torque
setting is switched to auxiliary torque setting mode. Its function is equivalent to
setting the one’s placeof FA-00=1. After the terminal is off, it returns the previous
setting mode automatically.
Xi=34
Switch primary torque setting to regular setting
In torque control mode, if the function terminal is on, then the special torque
setting is switched to the primary torque regular setting mode. Its function is
equivalent to setting the ones place of FA-00=0. After the terminal is off, it
returns the previous setting mode automatically.
Xi=35
Switch regular torque input to numeric torque input
In regular speed control mode, if the function terminal is on, then the present
regular torque setting mode is switched to the numeric torque input. Its function is
equivalent to F5-11=0. After the terminal is off, it returns the previous setting
mode automatically.
Xi=36
Switch special PID to regular PID
In special PID control mode, if the function terminal is on, then the PID setting
mode is switched from special mode to regular mode. After it is off, it returns the
previous setting mode automatically. Its function is equivalent to Fb-00=0.
Xi=37
PID positive/negative function switch
In the process of process PID control operation, if the input signal of the function
terminal is on, then the function of PID regulator conducts positive/negative
function switch. Its function is equivalent to adjusting parameters of F4-05.
Xi=38
Preset process PID terminal 1
Xi=39
Preset process PID terminal 2
Xi=40
Preset process PID terminal 3
In preset process PID control mode, 3 function input terminals need to be defined
as preset process PID terminals. A preset PID setting voltage set in Fb-20
~
Fb-26
is selected correspondingly as the present setting frequency of inverter through
the state combination of these three terminals. Correlation between preset process
PID terminals and preset process PID setting is as shown in Table 7-2.
Table 7-2 Correlation between preset process PID terminals and preset process PID
setting
Terminal 3 Terminal 2
Terminal 1
PID Given Voltage
Setting
Corresponding PID
Setting Code
OFF
OFF
OFF
Non-preset PID Setting
Defined by F4-00
OFF
OFF
ON
Preset PID Setting 1
Fb-20
OFF
ON
OFF
Preset PID Setting 2
Fb-21
OFF ON ON Preset
PID
Setting
3
Fb-22
ON
OFF
OFF
Preset PID Setting 4
Fb-23
ON OFF ON Preset
PID
Setting
5
Fb-24