6.2.7
Group C0: Monitoring Parameters
No.
Function
Range
Unit
Default
Type
C0-00
Output Frequency
0.00~Fup/0.0~Fup
Hz
512
×
C0-01
C0-02 Output
Frequency
Torque Upper Limit
Frequency
0.00~Fmax/0.0~Fmax Hz
514
×
C0-03
C0-04
Synchronous
Frequency
0.00~Fup/0.0~Fup Hz
516
×
C0-05
C0-06~ C0-07 Not Used
C0-08
Estimated Feedback
Frequency
0.00~Fup/0.0~Fup Hz
520
×
C0-09
C0-10
Estimated Slip
Frequency
0.00~Fup/0.0~Fup Hz
522
×
C0-11
C0-12
Output Current
Percentage
0.00~100.00 %
524
×
C0-13
Effective Output
Current Value
0.0~3000.0 A
525
×
C0-14
Output Voltage
Percentage
0.00~100.00 %
526
×
C0-15
Effective Output
Voltage Value
0.0~660.0 V
527
×
C0-16 DC
Bus
Voltage
0~1200
V
528
×
C0-17 Overload
Count
0.00~100.00
%
529
×
C0-18 Not
Used
C0-19
Program Operation
Section
1~7 SECT
531
×
C0-20
Running Time of
Present Section of
Program Operation
0.0~6000.0 S/min
532
×
C0-21 Output
Power
0.0~3000.0
kW
533
×
C0-22 PID
Input
0.00~10.00
V
534
×
C0-23
PID Calculation
Feedback
0.00~10.00 V
535
×
C0-24
Torque Current Input
I
q
*
0.00~200.00 %
536
×
C0-25
Torque Current
Feedback I
q
0.00~200.00 %
537
×
C0-26 Input
Terminal
Status
X7 X6
X5
X4
X3 X2
X1
538 ×
0 0 0 0 0 0 0
C0-27
Output Terminal
Status
* * * * R1
Y2
Y2
539 ×
0 0 0 0 0 0 0
C0-28
VS Input Monitoring
0-10000
540
×
C0-29
IS Input Monitoring
0-10000
541
×
C0-30
VF Input Monitoring
0-10000
542
×
C0-31
IF Input Monitoring
0-10000
543
×