User Manual
EM303A General Purpose Inverter
48
6.2.2
Group F1: Motor Parameters
No.
Function
Range
Unit
Default
Type
F1-00 Motor
Type
0: AC induction motor
1: Not used
0
〇
F1-01
Motor Rated Power
0.40~480.00 kW
XXXX
〇
F1-02 Motor
Rated
Voltage
60~660
V XXX
〇
F1-03
Motor Rated Current
0.1~1500.0
A
XXXX
〇
F1-04
Motor Rated Frequency
20.00~600.00/20.0~6000.0
Hz
XXXX
〇
F1-05
Motor Rated Speed
1~30000
rpm
XXXX
〇
F1-06 Motor
Wiring
Mode
0: Y Wiring
1:
Δ
Wiring
X
〇
F1-07
Motor Rated Power Factor
0.50~0.99
X
〇
F1-08
Idling Excitation Current
0.1~1500.0
A
XXXX
〇
F1-09 Rated
Torque
Current
0.1~1500.0
A XXXX
〇
F1-10
Stator Resistance R1
0.01~300.00
Ω
XXXX
〇
F1-11
Rotator Resistance R2
0.01~300.00
Ω
XXXX
〇
F1-12
Stator& Rotor Leakage
Inductance Ls
0.1~3000.0 mH
XXXX
〇
F1-13
Stator& Rotor Mutual
Inductance Lm
0.1~3000.0 mH
XXXX
〇
F1-14 Motor
Efficiency
30.0~99.0
% XXXX
〇
F1-15 Autotuning
Parameters
0:No autotuning
1:Staionary autotuning
2: Rotational autotuning
0
〇
F1-16 Inverter
Address
0
~
247, 0
:
Broadcasting Address
1
〇
F1-17
Communication Bit Rate
0: 4800
1: 9600
2: 19200
3: 38400
bps 1
〇
F1-18
Communication Parity
Mode
0: No parity 1+8+1
1: Even parity 1+8+1+1
2: Odd parity 1+8+1+1
0
〇
F1-19
Master-slave
Communication Mode
0:The inverter is the slave
1:The inverter is the master
0
〇
F1-20
Master Writes the Address
of Slave Inverter
0:Primary Numeric Frequency
F0-07
1:Auxiliary Numeric Frequency
F9-06
0
〇
F1-21
Inverter Receiving
Proportion Coefficient
0.00~600.00 %
100.00
●
F1-22
Analog Input Gain K1
0.00~600.00
%
100.00
●
F1-23
Analog Input Gain K2
0.00~600.00
%
0.00
●
F1-24
Analog Input Gain K3
0.00~600.00
%
100.00
●
F1-25
Analog Input Gain K4
0.00~600.00
%
0.00
●
F1-26
Analog Input Gain K5
0.00~600.00
%
0.00
●
F1-27
Analog Input Gain K6
0.00~600.00
%
0.00
●
F1-28
Analog Input Gain K7
0.00~600.00
%
0.00
●
F1-29
Analog Input Gain K8
0.00~600.00
%
0.00
●
F1-30 Communication
Overtime
0
(
Disabled
)
0.1
~
60.0
S 0
●
F1-31 Not
Used