12 Communication Protocol of EM303A
12.1 Application Scope
1. Applicable series: EM303A
2. Applicable network: Support ModBus protocol, RTU format, with single-master
and multiple-slaves communication network of RS485 bus.
The typical RTU message frame format:
Start Bit
Device Address
Function Code
Data
CRC Parity
Stop Bit
T1-T2-T3-T4 8Bit
8Bit n*8Bit 16Bit T1-T2-T3-T4
Remarks:
It takes 8S for inverter to reset the default of F0-28, the high bytes first, then the low
bytes. The inverter would not response to communicational command in those 8S.
12.2 Physical Interface
RS485 asynchronous half-duplex communication mode
Default data format of keypad communication interface: 1-8-N-1, bits rate: 9600bps.
Default data format of RS485 terminal: 1-8-N-1
,
bits rate:9600bps.
Data format 1-8-N-1, 1-8-O-1, 1-8-E-1, bits rates: 4800bps, 9600bps, 19200bps, and
38400 bps.
12.3 Protocol Format
Command code 0x03: Read parameter and status byte of inverter.
Frame Structure of Sending Message
Transmit Sequence
Bytes Sent
0
≥
Idle periods of 4 bits
1 Address
code
1
2 Function
code
1
3
Register start address
(
H
)
2
4
Register start address
(
L
)
5 Register
number
(
H
)
2
6 Register
number
(
L
)
7 CRC
parity
(
L
)
2
8 CRC
parity
(
H
)
9
≥
Idle periods of 4 bits