User Manual
EM303A General Purpose Inverter
47
Time
F0-13
Jog Deceleration
Time
0.00~600.00 S/min
15.00
●
F0-14 Carrier
Frequency 1.000~16.000
kHz 2.000
●
F0-15 Torque
Boost
0: Automatic torque boost
1~10: Fixed torque boost curve
11~20: Oil pump motor boost curve
21~30: Synchronous motor boost
curve
31~34: Blower/water pump boost
curve
35: Customer defined V/F curve
scaling
35
●
F0-16
Maximum Frequency
Fmax: 20.00~600.00/20.0~6000.0
Hz
50.00
〇
F0-17
Upper Limit
Frequency
Fup: Fdown~Fmax
Hz
50.00
〇
F0-18
Lower Limit
Frequency
Fdown: 0.00~Fup/0.0~Fup
Hz
0.00
〇
F0-19
Start Mode Options
0: Normal start
1: Speed search start
0
〇
F0-20
Stop Mode Options
0: Ramp to stop
1: Coast to stop
0
〇
F0-21
Function Setting for
JOG/+- button
0: Jog running
1: Positive/Negative input switching
2: Disabled
0
〇
F0-22
Speed Monitoring
Options
0: Frequency Hz
1: Speed rpm
0
●
F0-23
Customer Defined
Scaling
0.01~600.00
30.00
●
F0-24
Forward/Reverse
Control Mode
0: Forward/Reverse Permitted
1: Reverse Prohibited
0
〇
F0-25 F/R
Deadband
0.00~600.00
S
0.00
〇
F0-26
Primary Speed
Setting Mode
0: Regular speed setting mode
1: Special speed setting mode
2: Process PID input mode
0
〇
F0-27
Menu Mode Options
0: Basic menu mode
1: Advanced menu mode
0
〇
F0-28 Default
Control
0: Disabled
1:Defaults Reset
(Remarks: Defaults reset takes 8S.)
0
〇
F0-29
Parameter Setting
Control
0:Parameter setting permitted
1:Parameter lock 0
2: Parameter lock 1
0
〇
F0-30 Inverter
Model
0: Model G
1: Model P
0
〇
F0-31 User
Password
0~65535
XXXXX
〇