control mode is in terminal control mode, when terminal X1 is on, inverter runs.
Xi=0
No function
This function can be used to block the terminal when its hardware breaks down.
Xi=1
RUN
When start/stop control mode is terminal control (F0-04=1), if the function terminal
is on, the inverter will run as per the setting value of F0-05.
Xi=2
F/R Forward/Reverse
When start/stop control mode is in terminal control mode (F0-04=1), if the
function terminal is on, the inverter will forward/reverse as per the setting value of
F0-05.
Xi=3
Preset Speed Terminal 1
Xi=4
Preset Speed Terminal 2
Xi=5
Preset Speed Terminal 3
Xi=6
Preset Speed Terminal 4
In preset speed control mode, 4 function input terminals can be defined as the
preset speed terminals. A preset speed set in F3-00
~
F3-14 is selected as the
present setting frequency of inverter by the programming coding of these 4
terminals. See 7.4 for preset speed options setting.
Xi=7
Acceleration/Deceleration Time Terminal 1
Xi=8
Acceleration/Deceleration Time Terminal 2
F0-09
,
F0-10
,
F3-15
~
F3-20 set acceleration/deceleration time 1
~
4, and select
corresponding acceleration/deceleration time 1~4 through programming
acceleration/deceleration terminals. See 7.4 for the correlation of
acceleration/deceleration time and its terminal.
Xi=9
Coast to stop
Inverter is running, if the function terminal is on, PWM output is locked
immediately, and then motor coasts to stop.
Xi=10
Inverter fault reset input
Inverter can be reset through fault reset terminal after inverter fault is cleared.
Xi=11
Forward Jog FJOG
Xi=12
Reverse Jog RJOG
Inverter will forward when terminal FJOG is on, reverse when terminal RJOG is
on, and will stop when FJOG and RJOG are on simultaneously. See 7.1 for detail
of Jog operation.
★
Reverse jog is disabled when reverse is prohibited.
Xi=13
UP: Terminal controls numeric frequency, stepping frequency rises.
Xi=14
DOWN: Terminal controls numeric frequency, stepping frequency drops.
During operation, if input frequency is in numeric frequency input mode, set
Xi=13, or Xi=14, its function changes the numeric frequency, its speed rate can
be set by UP/DOWN frequency and speed rate setting of F9-07. If it is in stepping
mode, the terminals are hot keys for stepping frequency. Its speed rate can be set
as acceleration /deceleration time.