User Manual
EM303A General Purpose Inverter
139
Appendix 1
Control Command 1
(
4000H
)
Data
Meaning
Data
Meaning
0000H
Inactive Command
0006H
Ramp to Stop
0001H
Forward Running
0007H
Coast to Stop
0002H
Reverse Running
0008H
Fault Reset
0003H
JOG Forward
0009H
+/- Input Switch
0004H JOG
Reverse 000AH Parameter
Reset
0005H
Slave-inverter Stops
000BH
Not Used
Control Command 2
(
4001H
)
:
Virtual Terminals from LSB to MSB are:
X1, X2, X3, X4, X5, X6, X7, VS, VF, IS, IF, Y1, Y2, R1.
Virtual
Terminals
R
1
Y
2
Y
1
IF
IS VF
VS
X
7
X
6
X
5
X
4
X
3
X
2
X1
Bit 15
14
13
12
11
10
9
8
7 6
5
4
3
2
1
0
Inverter Status 1(4100H):
Data
Meaning
Data
Meaning
0000H
Parameter Setting
0004H
Slave-inverter Stops
0001H
Slave-inverter Runs
0005H
JOG Stop
0002H
JOG Running
0006H
Fault Status
0003H Autotuning 0007H
Factory
Check