User Manual
EM303A General Purpose Inverter
135
Command Code 0x10
:
Edit function codes or control parameters of inverter
Frame Structure of Sending Message
Transmit Sequence
Bytes Sent
0
≥
Idle periods of 4 bits
1 Address
code
1
2 Function
code
1
3
Register start address
(
H
)
2
4
Register start address
(
L
)
5
Register number
(
H
)
2
6
Register number
(
L
)
7 Byte
Length
1
8
Register data
(
H
)
2* Register number
9
Register data
(
L
)
10
CRC parity
(
L
)
2
11
CRC parity
(
H
)
12
≥
Idle periods of 4 bits
Frame Structure of Receiving Message
Receive Sequence
Bytes Received
0
≥
Idle periods of 4 bits
1 Address
code
1
2 Function
code
1
3
Register start address
(
H
)
2
4
Register start address
(
L
)
5
Register number
(
H
)
2
6
Register number
(
L
)
7
CRC parity
(
L
)
2
8
CRC parity
(
H
)
9
≥
Idle periods of 4 bits
Command Code 0x08: Circuit Diagnosis and Setting
Frame Structure of Sending Message
Transmit Sequence
Bytes Sent
0
≥
Idle periods of 4 bits
1 Address
code
1
2 Function
code
1
3
Sub-function code
(
H
)
2
4
Sub-function code
(
L
)
5
Data
(
H
)
2
6
Data
(
L
)
7
CRC parity
(
L
)
2
8
CRC parity
(
H
)
9
≥
Idle periods of 4 bits
Содержание EM303A-011G/015P-3CB