User Manual
EM303A General Purpose Inverter
66
6.2.12
Group F9: Speed Setting Options
No.
Function
Range
Unit
Default
Type
F9-00
Function of STOP
Button
0: Stop in keypad start/stop mode
1: Stop in all start/stop modes
2: Stop in keypad start/stop mode,
external fault trips in other modes
0
〇
F9-01
Parameter Editing
Mode
0:Editable through keypad and RS485
1:Editable through keypad
2:Editable through RS485
0
〇
F9-02
Numeric Input
Control Mode
Ones place:
Numeric reference input control mode
0: Auto-save the change in RAM
(Press DATA/ENTER to save)
1: Auto-save the change in EEPROM
(Memory function at power failure)
Tens place:
Numeric reference input edit mode
0:Editable through UP/DOWN button
on keypad
1: Editable through UP/DOWN
terminals
2: Interrelate with start/stop
mode(F0-04=0
,
editable through
UP/DOWN button on keypad F0-04=1,
editable through UP/DOWN terminals)
3: Editable in both modes
4: Not editable in both modes
Hundreds place:
Keypad UP/DOWN button rate control
0: Automatic rate control (UP/DOWN
acting time integration)
1: Correspond to the setting UP/DOWN
rate
Thousands place:
Terminal UP/DOWN rate control
0: Automatic rate control
1: Correspond to the setting UP/DOWN
rate
Ten thousands place:
Stepping mode setting options(
auxiliary setting mode)
0: Special speed setting
1: Auxiliary speed setting
1000
〇
F9-03
Speed Setting Mode
Ones place: Integrated speed input mode
0: Primary speed setting mode
1: Auxiliary speed setting mode
2:Primary speed setting mode +
auxiliary speed setting mode
Tens place:
Speed setting mode under jog control
0: Jog numeric speed setting mode
000
〇