4 Installation
4.2 Electrical Connection
Manual
130
SIPART DR21
C73000-B7476-C143-08
4.2.2
Connection standard controller
D
Power supply connection
!
CAUTION
Pay attention to mains jumpering (see figure 4-2, page 122)!
- 6DR210x-5
(115/230 V AC)
=
+24 V
+5 V
U
REF
0.63 A slow-blow at 115 V
0.315 A slow-blow at 230 V
per controller
1)
L
N
Three-pin plug IEC 320 IV DIN 49457A
230 V
115 V
PE
L
N PE
115 or 230 V AC
DR21
6DR210x-5
Fusing of the supply line
to VDE 0411 part 1
EN61 010, part 1 max. 150 VA
Other loads on the same
control loop
Figure 4-10 Connection 115/230 V AC power supply
- 6DR210x-4
(24 V UC)
=
1.6A, slow-blow
per controller
1)
L
N
Special 2-pin plug, any polarity
U
L
= 24 V UC
+24 V
+5 V
U
REF
Fusing of the supply line
to VDE 0411 part 1
EN61 010, part 1 max. 150 VA
or U
L
≤
30 V
Other loads on the same
control loop
DR21
6DR210x-4
Figure 4-11 Connection 24 V UC power supply
1)
The connection between the PE conductor screw (figure4-8, item 5, page128) to ground must be established addition-
ally for high electromagnetic compatibility (EMC) in 115/230 V-controllers.
This connection must also be low resistive for high frequencies (Cu-band or Hf-strand). Alternatively at least 2.5 mm
2
flexible should be used.
Содержание SIPART DR21
Страница 1: ...SIPART DR21 C73000 B7476 C143 08 1 SIPART DR21 6DR 210 Edition 08 2010 Manual ...
Страница 2: ...SIPART DR21 C73000 B7476 C143 08 2 ...
Страница 16: ...1 General Part Fundamental control technology terms Manual 16 SIPART DR21 C73000 B7476 C143 08 ...
Страница 148: ...4 Installation 4 2 Electrical Connection Manual 148 SIPART DR21 C73000 B7476 C143 08 ...
Страница 180: ...5 Operation 5 5 CPU self diagnostics Manual 180 SIPART DR21 C73000 B7476 C143 08 ...
Страница 192: ...6 Commissioning 6 7 Manual setting of the control parameters Manual 192 SIPART DR21 C73000 B7476 C143 08 ...
Страница 234: ...9 General explanation of abbreviations for SIPART DR Manual 234 SIPART DR21 C73000 B7476 C143 08 ...
Страница 242: ...Manual 242 SIPART DR21 C73000 B7476 C143 07 ...