3 Functional description of the structure switches
3.6 Controller output structures (S2, S49 to S55)
Manual
98
SIPART DR21
C73000-B7476-C143-08
Y-display:
In switch position S54=2 the setting ranges heating/cooling are displayed with their setting
ratio [%]. Switching of the output stages is visible as a point in the display (10) and indicates
the setting range heating/cooling.
The
±
Δ
y
-
outputs can be assigned to the appropriate digital outputs with the structure switch
S57.
The analog output is assigned by the structure switch S56.
y = 0 to Y1 (cooling -
Δ
y)
period duration tM from 0 to 1000 s
minimum pulse pause, -length: tA
y = Y2 to 100% (h
Δ
y)
period duration tP from 0 to 1000s
minimum pulse pause, -length: tE
setting ratio
y
1
1
0,5
0,5
100 %
40%
0 %
+
Δ
y
―Δ
y
Y1
Heating
35%
Y2
Chapter y = Y1 to Y2
Dead zone no setting pulses
tA
tE
On
Off
On
Off
tM
tM
tP
tP
Cooling, example
with setting ratio = 50 %
Heating, example
with setting ratio = 50 %
Cooling
y-display
Continuous contact
clocking
Dead zone, no output
Cooling
Heating
to
to
Figure 3-24 Setting ratio, actuating pulses of two-position controller
Содержание SIPART DR21
Страница 1: ...SIPART DR21 C73000 B7476 C143 08 1 SIPART DR21 6DR 210 Edition 08 2010 Manual ...
Страница 2: ...SIPART DR21 C73000 B7476 C143 08 2 ...
Страница 16: ...1 General Part Fundamental control technology terms Manual 16 SIPART DR21 C73000 B7476 C143 08 ...
Страница 148: ...4 Installation 4 2 Electrical Connection Manual 148 SIPART DR21 C73000 B7476 C143 08 ...
Страница 180: ...5 Operation 5 5 CPU self diagnostics Manual 180 SIPART DR21 C73000 B7476 C143 08 ...
Страница 192: ...6 Commissioning 6 7 Manual setting of the control parameters Manual 192 SIPART DR21 C73000 B7476 C143 08 ...
Страница 234: ...9 General explanation of abbreviations for SIPART DR Manual 234 SIPART DR21 C73000 B7476 C143 08 ...
Страница 242: ...Manual 242 SIPART DR21 C73000 B7476 C143 07 ...