3 Functional description of the structure switches
3.4 Controller types (S1, S42 to S45)
Manual
64
SIPART DR21
C73000-B7476-C143-08
D
Display of the external setpoint w
E
With the Shift key (6) the digital x/w-display can be switched between the display levels
I
to
IV
depending on the position of S81.
In display level
II
the active w can be displayed, in display level
III
the main control variable
x1. The external setpoint w
E
is displayed in display level
IV
. The displayed active or inactive
setpoint can also be adjusted (see table 3-3).
The active setpoint- and actual value are displayed on the analog displays.
Structure
switches
Posi-
tion
Function
S81
Switching the w/x-digital display
Display order
I
II
III
IV
[0]
x/xv
w/wv
--
--
1
x/xv
w/wv
x1/xv
--
2
x/xv
w/wi1/wv
--
wE/wvE/wi2
3
x/xv
w/wi1/wv
x1/xv
wE/wvE/wi2
4
x/xv
--
--
--
5
--
w/wv
--
--
6
--
--
x1/xv
--
7
xv
wv
x1
w
Identification of the displayed variables by the w- or x-signal lamp:
1 = steady light, 0.5 = flashing light, 0 = off
Display order
I
II
III
IV
1
0
0.5 (0 at S81=6)
0
x-signal lamp
0
1
0
0,5
w-signal lamp
Table 3-3
Display levels (S81)
D
Operation with 2 or 3 setpoints
If tracking of the inactive setpoint to the active setpoint is blocked with S45 = 1, a multiple
setpoint operation (switching between wi, w
E
and SH is achieved (see table 3-4, page 65)
and table 3-5, page 66.
D
Controlled variable processing
A 2-component control is implemented (disturbance variable connection). With factors c1
and c3 the main controlled variable x1 can connect the auxiliary controlled variable x2 with
weighting.
Содержание SIPART DR21
Страница 1: ...SIPART DR21 C73000 B7476 C143 08 1 SIPART DR21 6DR 210 Edition 08 2010 Manual ...
Страница 2: ...SIPART DR21 C73000 B7476 C143 08 2 ...
Страница 16: ...1 General Part Fundamental control technology terms Manual 16 SIPART DR21 C73000 B7476 C143 08 ...
Страница 148: ...4 Installation 4 2 Electrical Connection Manual 148 SIPART DR21 C73000 B7476 C143 08 ...
Страница 180: ...5 Operation 5 5 CPU self diagnostics Manual 180 SIPART DR21 C73000 B7476 C143 08 ...
Страница 192: ...6 Commissioning 6 7 Manual setting of the control parameters Manual 192 SIPART DR21 C73000 B7476 C143 08 ...
Страница 234: ...9 General explanation of abbreviations for SIPART DR Manual 234 SIPART DR21 C73000 B7476 C143 08 ...
Страница 242: ...Manual 242 SIPART DR21 C73000 B7476 C143 07 ...