Status
4. inverter is ready
4.1. Deselect STO.
4.2. Check the following:
● The inverter signals "SBC is not active" (r9773.4 = 0).
● The inverter signals neither faults nor alarms of the safety functions
(r0945[0…7], r2122[0…7]).
You have performed the acceptance test of the SBC function.
Appendix
A.2 Examples of acceptance tests
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD
393