Restriction with SINAMICS G120 Power Modules
You cannot use all of the integrated safety functions when using the following Power Modules:
Power Module
Restriction
PM230 in degree of protec‐
tion IP55
Article numbers 6SL3223-0DE . . - . . A . :
The integrated safety functions are not possible.
Article numbers 6SL3223-0DE . . - . . G . :
The basic STO function is possible.
PM230 in degree of protec‐
tion IP20 and Push Through
Article numbers 6SL321 . -1NE . . - . . L . :
The integrated safety functions are not possible.
Article numbers 6SL321 . -1NE . . - . . G . :
The basic STO function is not possible.
Description
3.5 Restrictions when using safety functions
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD