5.12.4.2
Output signal and setting the test mode
Requirements
● You are online with STARTER or Startdrive.
● You have selected the extended functions via onboard terminals.
Procedure with STARTER
To set the fail-safe digital output, proceed as follows:
1. Press the "Safety inputs/outputs" button.
2. Press the "Output" button.
3. Interconnect the status signals of your choice with the fail-safe digital output. The
"Safestate"signal is described below.
The inverter logically combines the status signals according to the following rules:
– The inverter ignored inputs without interconnection.
– If none of the inputs is interconnected, then the output signal = 0.
4. Activate the test for the fail-safe digital output.
5. Select the test mode that is compatible with your application.
Commissioning
5.12 Setting extended functions
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD
169