STOP F
If a safety function is active
1)
, a STOP F initiates a STOP A or STOP B:
● Fault F01611 immediately initiates a STOP A.
● For message C01711, the inverter response depends on the active safety function:
– When STO is active, then the inverter initiates a STOP A.
– In all other cases, the inverter initiates a STOP B.
If none of the safety functions are active, then the inverter responds as follows:
● Fault F01611 immediately initiates a STOP A.
● There is no immediate stop response for message C01711. However, the message is kept.
When selecting a safety function, the inverter responds with a stop as described above.
1)
The SSM function is considered as active safety function if the SSM filter and the SSM
hysteresis have been enabled.
Operation
6.10 Stop responses
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD