5.9.1
Configuring PROFIsafe via basic functions
Telegram 30 is preset as default in the inverter.
Configuring the PROFIsafe address
You must set the PROFIsafe addresses in the inverter and in the higher-level control system
to the same value.
Figure 5-2
Example: PROFIsafe address 64 hex of the inverter in the STEP 7 hardware configuration
A
Figure 5-3
Configuring the PROFIsafe address with STARTER
The PROFIsafe address of the inverter must be unique in the higher-level control system and
within the network itself.
Parameter
Description
p9610
PROFIsafe address (factory setting: 0000 hex)
Commissioning
5.9 Configuring safety functions and PROFIsafe using STARTER
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
116
Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD