Signal
Cause
Remedy
Complete information on the messages is available in the List Manual.
F01625
Sign-of-life error in the Safety data Check that the control cabinet design and cable routing are both in
compliance with EMC regulations.
Check as to whether an inadmissible voltage, e.g. 230 V, is connected
at the Control Unit digital output.
Fault acknowledgment
1. Select STO, and then deselect again.
2. If it cannot be acknowledged, replace the Control Unit.
F01630
Brake control defective
Fault value r0949 provides more de‐
tailed information.
Depending on the fault value, check the following:
10, 11: p1278 ≠ 0, brake not connected, cable interrupted or ground
fault
20: Short-circuit in the brake winding
30, 31, 40: Brake not connected or a short-circuit in the brake winding
50: Fault in the Safe Brake Relay, in the Control Unit or in the Power
Module.
A01631
Motor holding brake / SBC configu‐
ration does not make sense
Check and correct the parameterization of the motor holding brake:
The following settings can result in this message:
● p1215 = 0 and p9602 = 1.
● p1215 = 3 and p9602 = 1.
F01640,
F01641
It has been identified that a compo‐
nent has been replaced, acknowl‐
edgment/data save is necessary
Corrective maintenance (Page 331)
F01649
Internal software error
1. Switch off the Control Unit power supply and then on again.
2. If it cannot be acknowledged, replace the Control Unit.
F01650
Acceptance test required
Acceptance tests for the safety functions (Page 209)
F01651
Synchronization, safety time slices
unsuccessful.
1. Switch off the Control Unit power supply and then on again.
2. If it cannot be acknowledged, replace the Control Unit.
F01653
PROFIBUS/PROFINET configura‐
tion error
Check the PROFIBUS or PROFINET configuration of the safety slot
on the master side and on the Control Unit.
A01654
PROFIBUS configuration differs
Check the PROFIsafe configuring in the higher-level control.
● Alarm value r2124 = 1:
In the higher-level F control, remove the PROFIsafe configuring,
or enable PROFIsafe in the drive.
● Alarm value r2124 = 2:
In the higher-level F control, configure the appropriate PROFIsafe
telegram.
F01655
Aligning the monitoring functions
1. Check that the control cabinet design and cable routing are in
compliance with EMC regulations.
2. Switch off the Control Unit power supply and then on again.
F01656
Parameter processor 2 incorrect
1. Recommission the safety functions.
2. If this is not successful, then replace the Control Unit.