RTU303xC
Operating Instructions, 06/2019, C79000-G8976-C382-06
377
Syslog Messages
D
D.1
Structure of the Syslog Messages
The Syslog server collects log information of the devices and informs you about specific
events. The Syslog messages are transmitted via the set UDP port (standard 514) according
to RFC 5424.
Syslog messages log information when the device is accessed. Information can be status
information such as the origin of the message or a time stamp. The Syslog protocol
prescribes a fixed sequence and structure of the possible parameters.
The Syslog message consists of the following parameters:
Parameter
Explanation
HEADER
PRI
PRI contains the coded priority of the Syslog message, broken down into Severity (severity of the
message) and Facility (origin of the message).
VERSION
Version number of the Syslog specification.
TIMESTAMP
The device sends the time stamp in the format "2010-01-01T02:03:15.0003+02:00" as the local
time including the time zone and correction for daylight saving / standard time if needed.
HOSTNAME
The station name configured in the "System" tab for the RTU.
APP-NAME
Device or application from which the message originates.
"-" is output if information is missing.
PROCID
The process ID serves to clearly identify the individual processes, for example during analysis
and troubleshooting.
"-" is output if information is missing.
MSGID
ID to identify the message. "-" is output if information is missing.
STRUCTURED-DATA
timeQuality
The structured data element "timeQuality" provides information on system time. Example:
[timeQuality tzKnown="0" isSynced="0"]
The "tzKnown" parameter indicates whether the sender knows its time zone (value "1" = known;
value "0" = unknown).
The "isSynced" parameter indicates whether the sender is synchronized with a reliable external
time source, e.g. via NTP (value "1" = synchronized; value "0" = not synchronized).
MSG
MESSAGE
Message as ASCII string (English)
Note
Additional information
You can read more detailed information on the structure of the Syslog messages and on the
meaning of the parameters in RFC 5424.
https://tools.ietf.org/html/rfc5424
Содержание Simatic RTU3030C
Страница 248: ...Configuration WBM 4 24 Tag tables RTU303xC 248 Operating Instructions 06 2019 C79000 G8976 C382 06 ...
Страница 350: ...Dimension drawings RTU303xC 350 Operating Instructions 06 2019 C79000 G8976 C382 06 Figure B 2 Side view ...
Страница 376: ...Accessories C 7 Overvoltage protection modules RTU303xC 376 Operating Instructions 06 2019 C79000 G8976 C382 06 ...
Страница 390: ...Documentation references E 10 10 RTU303xC 390 Operating Instructions 06 2019 C79000 G8976 C382 06 ...